4.2.3 Overview of factory-set parameter settings

0 Access authority
00 Authorisation level
1 Weather-dependent set value regulation
00 Lowest ambient temperature (Lo_A)
01 Highest ambient temperature (Hi_A)
02 Target value at lowest ambient temperature
03 Target value at highest ambient temperature
2 Anti-legionella system
00 Operating interval
01 Status
02 Starting time
03 Target value
04 Holding time
3 Automatic restart
00 Status
4 Operation of optional additional heating and switch-off temperature for room heating
00 Status
01 Priority
02 Switch-off room heating in the summer
03 Restricted operation of optional additional heater
04 (Not configurable, fixed value)
5 Bivalence temperature and priority temperature of room heating
00 Status bivalence temperature
01 Bivalence temperature
02 Priority for room heating
03 Priority temperature of room heating
04 Target value correction for hot water
6 Hysteresis (DT) for water heating
00 Start
01 Stop
02 (Not configurable, fixed value)
7 Step length for hot water
00 Step length for hot water
01 Hysteresisvalue booster heater (BOH)
02 Status control on the basis of 2 target values
03 Control on the basis of 2 target values:
04 Control on the basis of 2 target values:
BA ROTEX HPSU compact 2 - 04/2011
Parameter name
(1
2. Target value for heating
2. Target value for cooling
4
x
Parameter settings
Default factory settings
Value
Range
Increment
3
2 - 3
1
-10
-20 - 5
1
15
10 - 20
1
40
25 - 55
1
25
25 - 55
1
FR
every day
1
0 - 1
23:00
0:00 - 23:00
1:00
70
40 - 80
5
10
5 - 60
5
0
0 - 1
1
0 - 1
0
0 - 2
35
14 - 35
1
3
0 - 3
2
1
0 - 1
0
-15 - 35
1
0
0 - 1
0
-15 - 20
1
10
0 - 20
1
2
2 - 20
1
2
0 - 10
1
0
0
0 - 4
1
2
2 - 20
1
Removed. Do not change the default value.
Removed. Do not change the default value.
Removed. Do not change the default value.
Unit
°C
°C
°C
°C
h
°C
min.
°C
°C
°C
°C
°C
°C
43