geminox FCX 22 C Technical Instructions page 22

Boiler water capacity up to 25l
Hide thumbs Also See for FCX 22 C:
Table of Contents

Advertisement

5.3.3.1 - Examples of installations with a 45°
bend and a 90° bend at the boiler out-
let
5.3.3.1.1 - Straight configuration
Refer to section 5.1 - page 15 - chapter V -
Fig. 16
INSTALLATION for other outlet configurations
90° elbow
45° elbow
View from above
rear boiler
Accessories :
- 1 45° concentric elbow Ø 80/125 (3.15/4.92 inch)
- 1 90° concentric elbow 
Ø 80/125 (3.15/4.92 inch),
- concentric extensions Ø 80/125 (3.15/4.92 inch),
- 1 concentric vertical terminal 
Ø 80/125 (3.15/4.92 inch),
- 1 vertical terminal fastening collar (supplied with
the vertical terminal),
- 1 sleeve tile adaptable according to the type of
roof covering and the roof slope,
,
- 1 roof plate
- 3 Ø 125 (4.92 inch) fastening collars,
Lmax = L1 + 1 m + 0,5 
Lmax = L1 + 3.28ft + 1.6ft 
Note:
- Each 45° elbow added reduces the maximum au-
thorised length by 0.5 m. (1.6 ft)
- Each 90° elbow added reduces the maximum au-
thorised length by 1m (3.28 ft).
5.3.3.1.2 - Straight configuration
Fig. 17
L
1
Accessoires :
- 1 45° concentric elbow Ø 80/125 (3.15/4.92 inch)
- 1 90° concentric elbow 
- 3 concentric extensions 
- 2 45° concentric elbow 
- 1 concentric vertical terminal 
- 1 vertical terminal fastening collar (supplied with
- 1 sleeve tile adaptable according to the type of
- 1 roof plate
9 m
- 3 Ø 125 (4.92 inch) fastening collars
29.5 ft
Lmax = L1 + 0,5 m + L2 + 0,5 m+ L3 + 1 m + 0,5 
Lmax = L1 + 1.6ft + L2 + 1.6ft+ L3 + 3.28ft + 1.6ft 
Note:
- Each 45° elbow added reduces the maximum au-
- Each 90° elbow added reduces the maximum au-
- 22 -
Refer to section 5.1 - page 15 - chapter V -
INSTALLATION for other outlet configurations
90° elbow
45° elbow
View from above
rear boiler
Ø 80/125 (3.15/4.92 inch),
Ø 80/125 (3.15/4.92 inch),
Ø 80/125 (3.15/4.92 inch),
Ø 80/125 (3.15/4.92 inch),
the vertical terminal),
roof covering and the roof slope,
,
thorised length by 0.5 m (1.6 ft).
thorised length by 1m (3.28 ft).
INSTALLATION
L
1
L
2
L
3
9 m
29.5ft

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fcx 30 c

Table of Contents