Advertisement

5.3.2.1.3 - Rigid flue with elbow
Fig. 14
90° elbow
45° elbow
view from above
rear boiler
Accessory:
- 1 angled horizontal balanced flue kit - l = 3 m
(9.8 ft),
Note :
- Use either the 45° bend or the 1 m (3.28 ft) exten-
sion at boiler outlet according to the system de-
sign.
5.3.3 - Drainage by vertical balanced flue
In addition to the flue installation guide-lines mentio-
ned above, the vertical flue terminal must leave a
minimal 30 cm (0.98 ft) gap between the roof level
(sloping or flat) and the air intake zone.
130
The distance between two terminals is also regula-
ted: it is advised to position two adjacent terminals
in the same horizontal plane. If this is not appli-
cable, the axis of the lower terminal must be at least
0.60 m (1.97 ft) clear of the closest point of the air
inlet of the higher terminal
Maximum length of the vertical conduit = 9 m
Fig. 15
GEMINOX recommendations
!
- 21 -
(29.5 ft)
60 cm
mini
It is advised to use 45° elbows rather
than 90° elbows.
INSTALLATION
30 cm
mini
FCX-19-0