UL/c-UL Approval
<Cautions>
Be aware of the following items when building the
GP unit into an end-use product:
• For use on a flat surface of a Type 4X (Indoor Use
Only) and/or Type 13 Enclosure.
• The temperature rating of field installed
conductors: 75°C only.
• Must be used with a Class 2 Power Supply. (24
VDC)
• For use in Pollution Degree 2 environment, or
equivalent.
• Surrounding air temperature rating 50°C
maximum or equivalent.
<Compliance and Handling Cautions in Hazardous
Locations>
• SUITABLE FOR USE IN CLASS I, DIVISION 2,
GROUPS A, B, C AND D HAZARDOUS
LOCATIONS, OR NONHAZARDOUS
LOCATIONS ONLY.
• WARNING - EXPLOSION HAZARD -
SUBSTITUTION OF ANY COMPONENTS MAY
IMPAIR SUITABILITY FOR CLASS I, DIVISION
2.
• WARNING - EXPLOSION HAZARD - DO NOT
DISCONNECT EQUIPMENT WHILE THE
CIRCUIT IS LIVE OR UNLESS THE AREA IS
KNOWN TO BE FREE OF IGNITABLE
CONCENTRATIONS.
• Control Drawing of USB port A (USB1) I/F
The information below concerns the use of the
USB I/F used in Class I, Division 2 Groups A, B,
C, and D hazardous locations (from Doc No.
3910017-USB).
USB Pin Description
1. Vcc
2. D-
3. D+
4. GND
(See Note 1 for details)
Shield GND
1
2
3
Associated Nonincen-
dive Field Wiring
Apparatus
Notes:
1. Nonincendive Circuit Parameters:
USB I/F:
Voc = 5.25 V
Isc = 0.7 A
Nonincendive
Field
Wiring
Apparatus
4
Ca = 16 µF
La = 10 µF
2. Selected Associated Nonincendive Field Wiring
Apparatus shall satisfy the following:
Nonincendive
Field
Wiring
Apparatus
Voc
Isc
Ca
La
3. If the electrical parameters of the cable are
unknown, the following values may be used:
Capacitance = 60 pF/ft
Inductive = 0.20 µH/ft
4. Nonincendive Field Wiring must be installed in
accordance with article 501.10(B) of the National
Electrical Code ANSI/NFPA 70.
5. Nonincendive Field Wiring Apparatus shall not con-
tain or be connected to another source of power.
• Mini USB port (USB2) is for temporary connection
only during maintenance and setup of the device.
Do not use, connect, or disconnect unless area is
known to be non-hazardous. Connection or
disconnection in an explosive atmosphere could
result in an explosion.
7
Associated
Nonincendive Field
-
Wiring Apparatus for
Graphic Panel
Vmax
lmax
Ci + C cable
Li + L cable