P1-P839, P2-P897 mA High Trim
If the device you are connected to is not calibrated, and not showing the correct
high value (reading), then you can trim it using this parameter. You can either
type in the offset directly, or use the up/down arrow keys to move the output up
and down until you get the expected result (reading) on the device that is
connected.
P1-P840, P2-P898 mA Fail-safe Mode
This parameter determines what happens to the mA output in the event of the unit
going into fail-safe mode. The default is to do the same as the system fail-safe
(P808/P1808), but this can be overridden to force the mA output to an independent
fail-safe mode as follows:
Option
0 = Default
1 = Hold
2 = Low
3 = High
P1-P841, P2-P899 mA Allocation
By default the mA output will be representative of the reading obtained, as
determined by the Mode P100/P1100. When P100/P1100 = 4 (Average) or 5
(Differential) the mA output can be assigned to be representative of the level of
either of the two points of measurement This parameter is automatically set to the
correct default option when selecting the Mode P100 and Xducer (P101), and
under normal circumstances will not require changing.
The options, dependant on the value entered for Mode P100/P1100, are as
follows:
Option
1 = Xducer 1 (Def. P1)
2 = Xducer 2 (Def. P2)
Description
mA output will fail as per P808/P1808.
mA output will retain its last known value.
mA output will fail to its low condition.
mA output will fail to its high condition.
Description
mA output relates to Xducer 1 level.
mA output relates to Xducer 2 level.
Page 109