Atlas Copco ga55+ Instruction Book page 91

Oil-injected rotary screw compressors
Hide thumbs Also See for ga55+:
Table of Contents

Advertisement

Instruction book
Reference
BV2
HE
E
Co
1
BV2 starts closing the bypass line and opening the oil supply line from the ER heat exchanger (HE) at the
lower limit of its temperature range. At the upper limit of its temperature range, the bypass line is completely
closed and all the oil flows through the ER heat exchanger.
On compressors versions with a maximum pressure lower than 13 bar, BV2 starts opening at 40 °C and is
completely open at 55 °C .
On compressors with a maximal pressure of 13 bar , BV2 starts opening at 60 °C and is completely open at 75
°C.
The housing of BV2 is provided with a special handle (V1), allowing to control the working of the energy
recovery system.
As can be seen on the ER label, the ER unit is integrated in the oil circuit and will recover energy when the
handle is completely turned in clockwise.
When the handle is turned out anticlockwise, the heat exchanger (HE) is bypassed and no energy will be
recovered.
9096 3313 00
Designation
Thermostatic bypass valve of ER unit
Oil/water heat exchanger (ER unit)
Compressor element
Oil cooler (compressor)
Water inlet
91

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ga75+Ga90

Table of Contents