Product Information 500 Series LSN Fire Detectors (EU)

7.2. General Notes for Detector Testing

FAP−OC 500
The
The CO sensor provides improved response behavior and increased stability against
nuisance alarms in critical environmental conditions.
For fire detection, FAP−500 detectors use the time behavior of the fire characteristics,
which differs from the time behavior of disruption variables.
Therefore, for a functional test, the detector must be switched to test mode. Switching
to test mode can occur in two ways, which are described in the alternative test proce-
dures (see below).
Detectors that are programmed for two−detector dependency must be
tested in accordance with the first alternative (in test mode).
For the detector test, you need:
− detector test device for optical fire detector (product ID 4.998.112.071)
− FAA−500−TTL test adapter with magnet (product ID F.01U.508.725).
For OC detector, in addition:
− CO testing gas for detector with CO sensor (product ID 4.998.142.221).
detector has an additional sensor for CO detection in case of fire.
Page 34
PI − 34.70 en
BDL−F.01U.025.876
A5.en/ 02.02.2006
ST−FIR/PRM1 / zab