Product Information 500 Series LSN Fire Detectors (EU)
Mounting notes for the external detector alarm display MPA
According to VdS guidelines, the external detector alarm display
must be mounted so that the flat side of the prism (Y) shows towards
the observer's line of sight.
19.
D Mounts directly on the ceiling or wall.
D For surface mounted cable entry (aP), break out the prepared cable entry points
(see Fig. 19., Pos. X) on the housing. For flush mounted cable entry (uP), cable
entry is through the opening below the connection board.
Connecting the external detector alarm display
The external detector alarm display is connected using 4 Wago terminals.
Connecting:
Disconnecting: pull out the wire while turning it to and fro.
Up to 4 detectors can be connected to each external detector alarm display.
Three inputs (T. 2 − 4) allow adjustment to the various line networks.
Making the connection depending on the line technology used
Line technology Fire panels
GLT
GLT
LSN
60
1 2 3 4
55
MPA
insert the stripped cable end (no braided wire) into the terminal.
BZ 1060
UEZ 1000, UGM 2020, FP 102, 104, 106
BZ 500 LSN, UEZ 1000, UEZ 2000 LSN,
UGM 2020, FPA−5000
Page 28
PI − 34.70 en
85
A
Y
A
Y
Terminals
T.1 + T.2
T.1 + T.3
T.1 + T.4
BDL−F.01U.025.876
A5.en/ 02.02.2006
ST−FIR/PRM1 / zab
X