Advertisement

NOTICE
Precautions when connecting field piping. Add brazing
material as shown in the figure.
≤Ø25.4
1
1
NOTICE
▪ Be sure to use the supplied accessory pipes when
carrying out piping work in the field.
▪ Be sure that the field installed piping does not touch
other pipes, the bottom panel or side panel. Especially
for the bottom and side connection, be sure to protect
the piping with suitable insulation, to prevent it from
coming into contact with the casing.
Connection from the stop valves to the field piping can be done by
using accessory pipes supplied as accessory.
The connections to the branch kits are the responsibility of the
installer (field piping).
6.4.5

To connect the multi connection piping kit

NOTICE
Improper installation may lead to malfunction of the
outdoor unit.
▪ Install the joints horizontally, so that the caution label (a) attached
to the joint comes to the top.
▪ Do not tilt the joint more than 7.5° (see view A).
▪ Do not install the joint vertically (see view B).
7.5°
A
7.5°
a
a
Caution label
X
Not allowed
O
Allowed
▪ Make sure that the total length of the piping connected to the joint
is absolute straight for more than 500 mm. Only if a straight field
piping of more than 120 mm is connected, more than 500 mm of
straight section can be ensured.
RXYTQ8~16T7YF
VRV IV system air conditioner
4P388989-1B – 2016.02
>Ø25.4
1
2
2
1
B
a
6.4.6

Multiple outdoor units: Knockout holes

Connection
Front connection
Remove the front plate knockout holes to
connect.
Bottom connection
Remove the knockout holes on the bottom
frame and route the piping under the bottom.
6.4.7

To connect the refrigerant branching kit

For installation of the refrigerant branching kit, refer to the installation
manual delivered with the kit.
▪ Mount the refnet joint so that it branches either horizontally or
vertically.
▪ Mount the refnet header so that it branches horizontally.
b
a
A
a
B
a
Horizontal surface
b
Refnet joint mounted vertically
c
Refnet joint mounted horizontally
6.4.8

To protect against contamination

Protect the piping as described in the following table to prevent dirt,
liquid or dust from entering the piping.
Unit
Installation period
Outdoor unit
>1 month
<1 month
Indoor unit
Regardless of the
period
Block all gaps in the holes for passing out piping and wiring using
sealing material (field supply) (otherwise the capacity of the unit will
drop and small animals may enter the machine).
Example: passing piping out through the front.
6 Installation
Description
c
Protection method
Pinch the pipe
Pinch or tape the pipe

Installer and user reference guide

19