To Charge Refrigerant; Step 6: To Manually Charge Refrigerant - Daikin RXYTQ8T7YF Installer And User Manual

Vrv iv system
Hide thumbs Also See for RXYTQ8T7YF:
Table of Contents

Advertisement

6 Installation
6.7.5

To charge refrigerant

Follow the steps as described below.
Pre-charging refrigerant
1 Calculate the additional amount of refrigerant to be added using
the formula mentioned in
refrigerant amount" on
page 24.
2 The first 10 kg of additional refrigerant can be pre-charged
without outdoor unit operation.
If
The additional refrigerant amount
is smaller than 10 kg
The additional refrigerant charge
is larger than 10 kg
3 Pre-charging can be done without compressor operation, by
connecting the refrigerant bottle to the service ports of the liquid
and equalising stop valves (open valve B). Make sure that valve
A and all outdoor unit stop valves are closed.
NOTICE
During pre-charging, the refrigerant is charged through the
liquid line. Close valve A and disconnect the manifold from
the gas line.
p <
p >
A
B
g
a
f
d
C
N2
R410A
b
c
e
a
Pressure reducing valve
b
Nitrogen
c
Weighing scales
d
Refrigerant R410A tank (siphon system)
e
Vacuum pump
f
Liquid line stop valve
g
Gas line stop valve
A
Valve A
B
Valve B
C
Valve C
4 Do one of the following:
If
4a
The calculated additional
refrigerant amount is reached
by above pre-charging
procedure
4b
The total amount of
refrigerant could not be
charged by pre-charging
INFORMATION
If the total additional refrigerant amount was reached in
step  3 (by pre-charging only), record the amount of
refrigerant that was added on the additional refrigerant
charge label provided with the unit and attach it on the
back side of the front panel.
Perform
the
test
"8 Commissioning" on
page 38.
Charging refrigerant
5 After pre-charging, connect valve A to the refrigerant charge
port and charge the remaining additional refrigerant through this
port. Open all outdoor unit stop valves. At this point, valve A
must remain closed!
Installer and user reference guide
26
"6.7.3  To determine the additional
Then
Perform steps 2+3.
Perform steps 2~8.
Then
Close valves C and B and
disconnect the manifold
connection to the liquid line.
Close valves C and B,
disconnect the manifold
connection to the liquid line,
and perform steps 4~8.
procedure
as
described
p <
p >
A
d
b
R410A
a
c
a
Weighing scales
b
Refrigerant R410A tank (siphon system)
c
Vacuum pump
d
Refrigerant charge port
A
Valve A
INFORMATION
For a multi outdoor unit system, it is not required to
connect all charge ports to a refrigerant tank.
The refrigerant will be charged with ±22 kg in 1 hour time
at an outdoor temperature of 30°C DB or with ±6 kg at an
outdoor temperature of 0°C DB.
If you need to speed up in case of a multiple outdoor
system, connect the refrigerant tanks to each outdoor unit.
NOTICE
▪ The refrigerant charging port is connected to the piping
inside the unit. The unit's internal piping is already
factory charged with refrigerant, so be careful when
connecting the charge hose.
▪ After adding the refrigerant, do not forget to close the
lid of the refrigerant charging port. The tightening
torque for the lid is 11.5 to 13.9 N•m.
▪ In order to ensure uniform refrigerant distribution, it
may take the compressor ±10 minutes to start up after
the unit has started operation. This is not a malfunction.
6 Proceed with the manual charge.
INFORMATION
After charging refrigerant:
▪ Record the additional refrigerant amount on the
refrigerant label provided with the unit and attach it to
the backside of the front panel.
▪ Perform
"8 Commissioning" on
6.7.6

Step 6: To manually charge refrigerant

The remaining additional refrigerant charge can be charged by
operating the outdoor unit by means of the manual refrigerant
charge operation mode:
1 Take all the precautions mentioned in
page 31
and
"8 Commissioning" on page 38
2 Turn on the power of the indoor units and outdoor unit.
3 Activate outdoor unit setting [2‑20]=1 to start manual refrigerant
charge mode. Refer to
page 34
for details.
Result: The unit will start operation.
4 Valve A can be opened. Charging of remaining additional
refrigerant can be done.
in
5 When the remaining calculated additional refrigerant amount is
added, close valve A and push BS3 to stop the manual
refrigerant charging procedure.
the
test
procedure
described
page 38.
"7  Configuration"  on
into account.
"7.2.8  Mode 2: Field settings"  on
RXYTQ8~16T7YF
VRV IV system air conditioner
4P388989-1B – 2016.02