G. Vent Diagrams
1. Top Vent - Horizontal Termination
One Elbow
Note: Use SLP Series
components only.
Fire Risk.
• When using SLP-HRC-SS termination cap on top
vented fi replaces, a one foot minimum vertical
vent section is required before installing first
elbow.
• Elbow heat shield required when V1 is less than
1-1/2 ft. Clearances to combustibles MUST be
maintained. See Section 5.A.
**
Note: When using SLP-FLEX (6-5/8 in.) venting, there
MUST be a 25% reduction in total H when using fl ex vent.
When using SLP-FLEX7 (7 in.) venting, refer to the venting
tables included with the adapter collar kit.
Figure 4.7
16
Majestic • MERC32IN, MERC32IL, MERC32VN, MERC32VL Installation Manual • 2401-980 Rev. C • 11/16
WARNING*
H
1
*
V
Minimum
H
Maximum
1
1
90 Elbow Only
2 ft.
1/2 ft.
152 mm
2 ft.
1-1/2 ft.
457 mm
3 ft.
2-1/2 ft.
762 mm
5 ft.
3-1/2 ft.
1.1 m
7 ft.
4-1/2 ft.
1.4 m
15 ft.
H
MAX. =15 ft. (4.6 m)
1
V
+ H
MAX. = 40 ft. (12.2 m)
1
1
*
See Warning.
V
1
**
610 mm
610 mm
914 mm
1.5 m
2.1 m
4.6 m