Connecting the Refrigerant Pipe

There are two refrigerant pipes of differing diameters:
A smaller one for the liquid refrigerant
A larger one for the gas refrigerant
The inside of copper pipe must be clean & has no dust.
1
Remove the pinch pipe on the pipes and connect the assembly pipes to
each pipe, tightening the nuts, first manually and then with a wrench, a
spanner applying the following torque.
Outer Diameter
6.35 mm (1/4")
9.52 mm (3/8")
12.70 mm (1/2")
15.88 mm (5/8")
19.05 mm (3/4")
22.23 mm (7/8")
N N
o o
t t
e e
N N
o o
t t
e e
If the pipes must be shortened refer to page 10.
2
Must use insulator which is thick enough to cover the refrigerant pipe to
protect the condensate water on the outside of pipe falling onto the floor
and the efficiency of the unit will be better.
3
Cut off any excess foam insulation.
4
Be sure that there must be no crack or wave on the bended area.
5
It would be necessary to double the insulation thickness(10mm or more)
to prevent condensation even on the insulator when if the installed area is
warm and humid.
Torque (kgf•cm)
144~176
333~407
504~616
630~770
990~1210
990~1210
Refrigerant oil
Torque wrench
Flare nut
Union
Insulation
refrigerant pipe
Clamp
Insulation
refrigerant pipe
Gas
refrigerant
pipe
Liquid refrigerant pipe
Spanner
9