Summary of Contents for PR 9106B

  • Page 1 9 1 0 6 B ® H A R T T r a n s p a r e n t R e p e a t e r N o . 9 1 0 6 V 1 0 1 - U K P r o d u c t v e r s i o n : 9 1 0 6 - 0 0 2 S I G N A L S T H E B E S T...
  • Page 2 PR electronics A/S tilbyder et bredt program af analoge og digitale signalbehandlingsmoduler til industriel automation. Programmet består af Isolatorer, Displays, Ex-barrierer, Temperaturtransmittere, Universaltransmittere mfl. Vi har modulerne, du kan stole på i selv barske miljøer med elektrisk støj, vibrationer og temperaturud- sving, og alle produkter opfylder de strengeste internationale stan- darder.
  • Page 3: Table Of Contents

    How to demount system 9000 ........... EC declaration of conformity ..........Technical characteristics ............ Applications ................ PR 4501 display / programming front ........ Visualisation in 4501 of hardware / software error .... 13 Connections ............... 14 Block diagram ..............15 Signal error indications without display front .....
  • Page 4: Warning

    Do not open the front plate of the device as this will cause damage to the connector for the display / programming front PR 4501. This device contains no DIP-switches or jumpers. SymBol idENTificATioN Triangle with an exclamation mark: Read the manual before installation and commissioning of the device in order to avoid incidents that could lead to personal injury or mechanical damage.
  • Page 5 Should there be any doubt as to the correct handling of the device, please contact your local distributor or, alternatively, PR electronics A/S www.prelectronics.com The use of stranded wires is not permitted for mains wiring except when wires are fitted with cable ends.
  • Page 6: How To Demount System 9000

    To the extent that the instructions in this manual are not strictly observed, the customer cannot advance a demand against PR electronics A/S that would otherwise exist according to the concluded sales agreement. HoW To dEmouNT SySTEm 9000...
  • Page 7: Ec Declaration Of Conformity

    Ec dEclARATioN of coNfoRmiTy As manufacturer PR electronics A/S lerbakken 10 dk-8410 Rønde hereby declares that the following product: Type: 9106B Name: HART transparent repeater ® is in conformity with the following directives and standards: The EMC Directive 2004/108/EC and later amendments...
  • Page 8: Technical Characteristics

    • 9106B can be mounted in the safe area or in zone 2 / Cl. 1, div. 2 and receive signals from zone 0, 1, 2 and zone 20, 21, 22 including mining / Class I/II/III, Div. 1, Gr. A-G.
  • Page 9: Applications

    APPlicATioNS Input signals: Output signals: Analogue, 4...20 mA Channel 1 Channel 1 2-wire transmitter Passive 2-wire Current Channel 2 Power rail Status relay signal Rail, +24 VDC Rail, Gnd. No connection No connection Power connection: Channel 2 Gnd. - 2-wire transmitter Supply +19.2...31.2 VDC Device status...
  • Page 10: Pr 4501 Display / Programming Front

    PR 4501 diSPlAy / PRogRAmmiNg fRoNT functionality The simple and easily understandable menu structure and the explanatory help texts guide you effortlessly and automatically through the configuration steps, thus making the product very easy to use. Functions and configuration options are described in the section ”Configuration / operating the function keys”.
  • Page 11 9106B: Type Barrier version unit channels 9106B Uo = 28 V ..: 1 Single ..: A Uo = 25.6 V. . . : 2 Double ..: B...
  • Page 12 Isolation - test / working: Input to any ..........2.6 kVAC / 300 VAC reinforced isolation Analogue output to supply ...... 2.6 kVAC / 300 VAC reinforced isolation Status relay to supply ......1.5 kVAC / 150 VAC reinforced isolation SMART bi-directional communication frequency range ..........
  • Page 13 current output: Signal range ..........3.5...23 mA Load (max.) ..........20 mA / 600 Ω / 12 VDC Load stability ..........≤ 0.01% of span / 100 Ω Current limit ..........≤ 28 mA Passive 2-wire output installation: Max. external 2-wire supply ......26 VDC Max. load resistance [Ω] ......(V - 3.5) / 0.023 A supply Effect of external 2-wire supply...
  • Page 14 Approvals: EMC 2004/108/EC ........EN 61326-1 LVD 2006/95/EC .......... EN 61010-1 c UL us, Standard for Safety ...... UL 61010-1 GOST R marine: Det Norske Veritas, Ships & Offshore ..Stand. f. Certific. No. 2.4 i.S. / Ex: ATEX 94/9/EC ..........DEKRA 11ATEX0244 X IECEx ............
  • Page 15: Visualisation In 4501 Of Hardware / Software Error

    4501 of hardware / software error Readout at hardware error Error search Readout Cause Communications test 4501 / 9106B NO.CO Connection error Configuration error or crc EEprom error - check configuration FL.ER mismatch, recovery configuration is loaded II ! / II !
  • Page 16: Connections

    coNNEcTioNS Power rail Supply and connections status relay 91 92 93 94 95 31 32 N.C. Gnd. Gnd. +24 V Error signal +24 V NC = no connection Ex inputs - SIL 2: 2-wire transmitter Current 2-wire transmitter Current Ex inputs - SIL 3: Current 2-wire transmitter Current...
  • Page 17: Block Diagram

    Block diAgRAm +24V Gnd. 9106 - Product Version 9106-002...
  • Page 18: Signal Error Indications Without Display Front

    Signal error indications without display front List of LED and error signal indications green ch. 1: ch. 2: Status relay, Power rail condition N.c. signal status Device OK Blinking Energized No supply De-energized Device defective Blinking De-energized Ch. 1 defective (ch. 2 OK) Blinking De-energized Ch.
  • Page 19: Configuration / Operating The Function Keys

    Documentation for routing diagram. in general When configuring the 9106B, you will be guided through all parameters and you can choose the settings which fit the application. For each menu there is a scrolling help text which is automatically shown in line 3 on the display.
  • Page 20 UK, DE, FR, IT, ES, SE and DK. Power rail: In the menu ”RAIL” you can choose if a signal is transmitted to the central surveillance in the PR 9410 power control unit when the signal limits are exceeded.. Safety integrity level (Sil): See Safety Manual for details.
  • Page 21: Routing Diagram

    RouTiNg diAgRAm If no key is activated for 1 minute, the display will return to the default state 1.0 without saving configuration changes. 1 Increase value / choose next parameter 2 Decrease value / choose previous parameter 3 Save the chosen value and proceed to the next menu Hold 3 Back to previous menu / return to menu 1.0 without saving Power up 0000...
  • Page 22: Routing Diagram, Advanced Settings (Adv.set)

    RouTiNg diAgRAm, ADVANCED SETTINGS (ADV.SET) DISP, PASS, LANG, RAIL A.OUT STAT DISP TAG1 TAG2 LOOP SETUP CONTRA LIGHT TAGNO TAGNO DISP Txt 6 Txt 9 Txt 10 Txt 11 Txt 11 Txt 12 9999 0000 PASS 0000 SETUP EN.PASS NEW.PAS Txt 6 Txt 15 Txt 16...
  • Page 23: Scrolling Help Texts In Display Line 3

    ScRolliNg HElP TEXTS iN diSPlAy liNE 3 [01] Set correct password [ PASS ] [02] Enter advanced setup [ ADV.SET ] [03] Set low limit for loop error detection [ LO.LIM1 ] [LO.LIM2 ] [04] Set high limit for loop error detection [ HI.LIM1 ] [HI.LIM2 ] [05] Enable rail status signal output? [ RAIL.ER ] [06]...
  • Page 24: Appendix

    APPENdiX iEcEx installation drawing ATEX installation drawing fm installation drawing Safety manual 9106 - Product Version 9106-002...
  • Page 25 LERBAKKEN 10, 8410 RØNDE DENMARK IECEx Installation drawing For safe installation of 9106B the following must be observed. The module shall only be installed by qualified personnel who are familiar with the national and international laws, directives and standards that apply to this area.
  • Page 26 9106QI01 LERBAKKEN 10, 8410 RØNDE DENMARK Hazardous area Non Hazardous area (terminal 11,12,13,14) Zone 0,1,2, 20, 21, 22 or Zone 2 (terminal 31,32,33,34) (terminal 91,92,93,94,95) -20 ≤Ta ≤ +60ºC : 253 V, max. 400 Hz 4501 9106 91 92 93 94 95 Power Rail 9106B1A, 9106B1B...
  • Page 27 9106QI01 LERBAKKEN 10, 8410 RØNDE DENMARK Hazardous area Non Hazardous area (terminal 11,12,13,14) Zone 0,1,2, 20, 21, 22 or Zone 2 (terminal 31,32,33,34) (terminal 91,92,93,94,95) -20 ≤Ta ≤ +60ºC : 253 V, max. 400 Hz 4501 9106 91 92 93 94 95 Power Rail 9106B1A, 9106B1B, 9106B2A, 9106B2B...
  • Page 28 9106QI01 LERBAKKEN 10, 8410 RØNDE DENMARK Hazardous area Non Hazardous area (terminal 11,12,13,14) Zone 0,1, 2, 20, 21, 22 or Zone 2 (terminal 31,32,33,34) (terminal 91,92,93,94,95) : 253 V, max. 400 Hz -20 ≤Ta ≤ +60ºC 4501 9106 91 92 93 94 95 Power Rail 9106B1A, 9106B1B...
  • Page 29 9106QI01 LERBAKKEN 10, 8410 RØNDE DENMARK (terminal 11,12,13,14) Hazardous area Non Hazardous area (terminal 31,32,33,34) Zone 0,1,2, 20, 21, 22 or Zone 2 (terminal 91,92,93,94,95) : 253 V, max. 400 Hz -20 ≤Ta ≤ +60ºC 4501 9106 91 92 93 94 95 Power Rail 9106B1A, 9106B1B, 9106B2A, 9106B2B...
  • Page 30 LERBAKKEN 10, 8410 RØNDE DENMARK ATEX Installation drawing For safe installation of 9106B the following must be observed. The module shall only be installed by qualified personnel who are familiar with the national and international laws, directives and standards that apply to this area.
  • Page 31 9106QA01 LERBAKKEN 10, 8410 RØNDE DENMARK Hazardous area Non Hazardous area (terminal 11,12,13,14) Zone 0,1,2, 20, 21, 22 or Zone 2 (terminal 31,32,33,34) (terminal 91,92,93,94,95) -20 ≤Ta ≤ +60ºC : 253 V, max. 400 Hz 4501 9106 91 92 93 94 95 Power Rail 9106B1A, 9106B1B...
  • Page 32 9106QA01 LERBAKKEN 10, 8410 RØNDE DENMARK Hazardous area Non Hazardous area (terminal 11,12,13,14) Zone 0,1,2, 20, 21, 22 or Zone 2 (terminal 31,32,33,34) (terminal 91,92,93,94,95) -20 ≤Ta ≤ +60ºC : 253 V, max. 400 Hz 4501 9106 91 92 93 94 95 Power Rail 9106B1A, 9106B1B, 9106B2A, 9106B2B...
  • Page 33 9106QA01 LERBAKKEN 10, 8410 RØNDE DENMARK Hazardous area Non Hazardous area (terminal 11,12,13,14) Zone 0,1, 2, 20, 21, 22 or Zone 2 (terminal 31,32,33,34) (terminal 91,92,93,94,95) : 253 V, max. 400 Hz -20 ≤Ta ≤ +60ºC 4501 9106 91 92 93 94 95 Power Rail 9106B1A, 9106B1B...
  • Page 34 9106QA01 LERBAKKEN 10, 8410 RØNDE DENMARK (terminal 11,12,13,14) Hazardous area Non Hazardous area (terminal 31,32,33,34) Zone 0,1,2, 20, 21, 22 or Zone 2 (terminal 91,92,93,94,95) : 253 V, max. 400 Hz -20 ≤Ta ≤ +60ºC 4501 9106 91 92 93 94 95 Power Rail 9106B1A, 9106B1B, 9106B2A, 9106B2B...
  • Page 35 LERBAKKEN 10, 8410 RØNDE DENMARK FM Installation drawing For safe installation of 9106B the following must be observed. The module shall only be installed by qualified personnel who are familiar with the national and international laws, directives and standards that apply to this area.
  • Page 36 9106QF01 LERBAKKEN 10, 8410 RØNDE DENMARK Hazardous Classified Location Unclassified Location or Hazardous Classified Location Class I/II/III, Division 1, Group A,B,C,D,E,F,G Zone 0,1, 2 Group IIC, IIB, IIA or Class I, Division 2, Group ABCD T4 Zone 20, 21 Class I Zone 2 Group IIC T4 -20 ≤Ta ≤...
  • Page 37 9106QF01 LERBAKKEN 10, 8410 RØNDE DENMARK Hazardous Classified Location Unclassified Location or Class I/II/III, Division 1, Group A,B,C,D,E,F,G Hazardous Classified Location Zone 0,1, 2 Group IIC, IIB, IIA or Class I, Division 2, Group ABCD T4 Zone 20, 21 Class I Zone 2 Group IIC T4 -20 ≤Ta ≤...
  • Page 38 9106QF01 LERBAKKEN 10, 8410 RØNDE DENMARK Hazardous Classified Location Unclassified Location or Hazardous Classified Location Class I/II/III, Division 1, Group A,B,C,D,E,F,G Zone 0,1, 2 Group IIC, IIB, IIA or Class I, Division 2, Group ABCD T4 Zone 20, 21 Class I Zone 2 Group IIC T4 -20 ≤Ta ≤...
  • Page 39 9106QF01 LERBAKKEN 10, 8410 RØNDE DENMARK Hazardous Classified Location Unclassified Location or Class I/II/III, Division 1, Group A,B,C,D,E,F,G Hazardous Classified Location Zone 0,1, 2 Group IIC, IIB, IIA or Class I, Division 2, Group ABCD T4 Zone 20, 21 Class I Zone 2 Group IIC T4 4501 -20 ≤Ta ≤...
  • Page 40: Safety Manual

    Safety manual HaRt tRanSPaRent RePeateR 9106 this safety manual is valid for the following product versions: 9106-002 Version No. V1R0...
  • Page 41 9106 HART ® transparent repeater Safety Manual 0. COntentS 1. Observed standards ................2. Acronyms and abbreviations ..............3. Purpose of the product ................4. Assumptions and restrictions for use of the product......4.1 Basic safety specifications ............. 4.2 Safety accuracy ................4.3 Analogue output ................
  • Page 42: Observed Standards

    9106 HART ® transparent repeater Safety Manual 1. Observed standards Standard Description Functional Safety of electrical / electronic / programmable IEC 61508 electronic safety-related systems IEC 61508- Part 2: Requirements for electrical / electronic / programmable 2:2000 electronic safety-related systems 2.
  • Page 43: Purpose Of The Product

    9106 HART ® transparent repeater Safety Manual 3. Purpose of the product HART transparent, galvanic isolation and repetition of passive and active 4...20 mA current signals from hazardous area to non-classified area. The module can be mounted in non-classified area or in zone 2 / Div. 2 and receive current signals from zone 0, 1, 2, 20, 21, 22 and mines or Class I/II/III, Div.
  • Page 44: Installation In Hazardous Areas

    9106 HART ® transparent repeater Safety Manual Installation in hazardous areas The IECEx Installation drawing, ATEX Installation drawing and FM Installation drawing shall be followed if the products are installed in or connected to hazardous areas. 4.6. Installation in SIl 3 applications The independence of the safety functions enables the use of the two channels in a 9106 HART ®...
  • Page 45: Safety Parameters

    9106 HART ® transparent repeater Safety Manual 7. Safety parameters Connection diagram Ex input SIL 2 Probability of dangerous Failure per Hour (PFH) 4.10E-08 Note Probability of failure on demand (PFD) - 1.95E-04 1 year proof test interval Proof test interval (10% of loop PFD) 5 years Safe Failure Fraction Demand mode...
  • Page 46: Hardware And Software Configuration

    9106 HART ® transparent repeater Safety Manual Connection diagram Ex input SIL 3 Probability of dangerous Failure per Hour (PFH) 1.10E-08 Note Probability of failure on demand (PFD) - 4.27E-05 1 year proof test interval Proof test interval (10% of loop PFD) 2 years Safe Failure Fraction Demand mode...
  • Page 47: Failure Category Sil 2 / Sil 3

    Any failures that are detected and that compromise functional safety should be reported to the sales department at PR electronics A/S. Repair of the module and replacement of circuit breakers must be done by PR electronics A/S only. 12. maintenance No maintenance required.
  • Page 48: Connections Diagram

    9106 HART ® transparent repeater Safety Manual 13. Connections diagram Power rail Supply and connections status relay 91 92 93 94 95 31 32 N.C. Gnd. Gnd. +24 V Error signal +24 V NC = no connection Ex inputs - SIL 2: 2-wire transmitter Current 2-wire transmitter...
  • Page 49 displays Programmable displays with a wide selection of inputs and outputs for display of temperature, volume and weight, etc. Feature linearisation, scaling, and difference measurement functions for programming via PReset software. Ex interfaces Interfaces for analogue and digital signals as well as HART signals between sensors / I/P converters / ®...
  • Page 50  sales@prelectronics.it  www.prelectronics.se  sales@prelectronics.se  www.prelectronics.co.uk  sales@prelectronics.co.uk  www.prelectronics.com  sales@prelectronics.com  www.prelectronics.cn  sales@prelectronics.cn Head office Denmark www.prelectronics.com PR electronics A/S sales@prelectronics.dk Lerbakken 10 tel. +45 86 37 26 77 DK-8410 Rønde fax +45 86 37 30 85...