Purpose Of The Product; Assumptions And Restrictions For Use Of The Product; Basic Safety Specifications; Safety Accuracy - PR 9106B Manual

Hart transparent repeater
Table of Contents

Advertisement

Safety Manual

3. Purpose of the product

HART transparent, galvanic isolation and repetition of passive and active 4...20
mA current signals from hazardous area to non-classified area.
The module can be mounted in non-classified area or in zone 2 / Div. 2 and
receive current signals from zone 0, 1, 2, 20, 21, 22 and mines or Class I/II/III,
Div. 1, Group. A-G.
Error events, including cable breakage, are monitored and signalled via the
individual status relay and/or a collective electronic signal via the power rail.
The display and programming module 4501 can be used to show the actual
process values, and alter the set point for high and low limit.
The 9106 has been designed, developed and certified for use in SIL applications
according to the requirements of IEC 61508

4. assumptions and restrictions for use of the product

4.1

Basic safety specifications

Operational temperature range ............ -20...+60°C
Storage temperature range .................. -20...+85°C
Power supply type. ............................... Double or reinforced
Supply voltage ...................................... 19.2...31.2 VDC
Loop supply 9106B1 ............................ 16V @ 20mA
Loop supply 9106B2 ............................ 15V @ 20mA
Max external output supply voltage ..... 26 VDC
Mounting area ....................................... Class I, Zone 2/Division 2 or safe area
Mounting environment .......................... Pollution degree 2,
4.2

Safety accuracy

The analogue output corresponds to the applied input within the safety
accuracy.
Safety accuracy .......................... ±2%
4.3

analogue output

The connected safety PLC shall be able to detect and handle the fault
indications from the analogue output of the 9106 Repeater by having a
NAMUR NE43-compliant input circuit.

4.4. failure rates

The basic failure rates from the Siemens standard SN 29500 are used
as the failure rate database.
Failure rates are constant, wear-out mechanisms are not included.
External power supply failure rates are not included.
9106 HART ® transparent repeater
Version No. V1R0
Overvoltage category II
3

Advertisement

Table of Contents
loading

This manual is also suitable for:

91069106a

Table of Contents