PR 9106B Manual page 38

Hart transparent repeater
Table of Contents

Advertisement

LERBAKKEN 10, 8410 RØNDE DENMARK
Hazardous Classified Location
Class I/II/III, Division 1, Group A,B,C,D,E,F,G
Zone 0,1, 2 Group IIC, IIB, IIA or
Zone 20, 21
Simple Apparatus or
Intrinsic safe apparatus
with entity parameters:
Vmax (Ui) ≥ Vt (Uo)
Imax (Ii) ≥ It (Io)
Pi ≥ Pt (Po)
Ca ≥ C
+ Ci
cable
La ≥ L
+ Li
cable
9106B1A, 9106B1B
Ex input: Loop current source 1 to 2
CH1 (terminal 44)
CH2 (terminal 52)
U
:
28 V
o
I
:
93 mA
o
P
:
0.65 W
o
IIC or A,B
IIB or C,E,F
C
0.08 F
o.
L
3 mH
o.
Revision date:
2011-11-02
+
T
-
IIA or D,G
0.600 F
2.15 F
12 mH
25 mH
Version Revision
V3 R0
9106 - Product Version 9106-002
Unclassified Location or
Hazardous Classified Location
Class I, Division 2, Group ABCD T4
Class I Zone 2 Group IIC T4
-20 ≤Ta ≤ +60ºC
44
43
CH1
42
41
54
53
CH2
52
51
91 92 93 94 95
Power
Rail
9106B2A, 9106B2B
Ex input: Loop current source 1 to 2
CH1 (terminal 44)
CH2 (terminal 52)
U
:
25.6 V
o
I
:
100 mA
o
P
:
0.64 W
o
IIC or A,B IIB or C,E,F
C
0.10 F
0.800 F
o.
L
2 mH
9 mH
o.
Prepared by:
PB
9106QF01
4501
34
33
32
31
14
13
12
11
9106
(terminal 11,12,13,14)
(terminal 31,32,33,34)
(terminal 91,92,93,94,95)
U
: 253 V, max. 400 Hz
m
IIA or D,G
2.75 F
15 mH
Page:
4/5
36

Advertisement

Table of Contents
loading

This manual is also suitable for:

91069106a

Table of Contents