Page 1
5 1 0 4 R e p e a t e r / P o w e r S u p p l y N o . 5 1 0 4 V 1 0 4 - U K F r o m s e r . n o . 0 3 0 2 5 0 0 0 1 S I G N A L S T H E B E S T...
Page 2
PR electronics A/S tilbyder et bredt program af analoge og digitale signalbehandlingsmoduler til industriel automation. Programmet består af Isolatorer, Displays, Ex-barrierer, Temperaturtransmittere, Universaltransmittere mfl. Vi har modulerne, du kan stole på i selv barske miljøer med elektrisk støj, vibrationer og temperaturud- sving, og alle produkter opfylder de strengeste internationale stan- darder.
General mounting, connection and disconnection of wires. Troubleshooting the device. Repair of the device and replacement of circuit breakers must be done by PR electronics A/S only. WARNING SYSTEM 5000 must be mounted on DIN rail according to DIN 46277.
SYmbOL IDENTIfIcATION Triangle with an exclamation mark: Warning / demand. Potentially le thal situations. The cE mark proves the compliance of the device with the essential requirements of the directives. The double insulation symbol shows that the device is protected by double or reinforced insulation.
LIAbILITY To the extent the instructions in this manual are not strictly observed, the custom er cannot advance a demand against PR electronics A/S that would otherwise exist according to the concluded sales agreement. 5104V 1 0 4 - UK...
Ec DEcLARATION Of cONfORmITY As manufacturer PR electronics A/S Lerbakken 10 Dk-8410 Rønde hereby declares that the following product: Type: 5104 Name: Repeater / Power Supply is in conformity with the following directives and standards: The EMC Directive 2004/108/EC and later amendments...
HOW TO DEmOUNT SYSTEm 5000 first, remember to demount the connectors with hazardous voltages. Picture 1: By lifting the bottom lock, the device is detached from the DIN rail. Picture 2: Then, by lifting the upper lock and pulling the front plate simultaneously the PCB is removed.
REPEATER / POWER SUPPLY PRetrans 5104 • 1- or 2-channel version • 3- / 5-port 3.75 kVAC galvanic isolation • Loop supply > 17.1 V • 20 programmable measurement ranges • Universal supply by AC or DC Application • Supply voltage and safety barrier for 2-wire transmitters mounted in a hazardous area.
Order: 5104 Type Version Input Output channels 5104 Standard : A 0...20 mA : A Special Single 4…20 mA : B 0...20 mA : 1 Double [EEx ia] II C 0...10 V 4…20 mA : 2 IS, DIV. 1 2...10 V 0...1 V Special 0.2...1 V...
Page 12
Accuracy, the greater of the general and basic values: General values Absolute Temperature Input type accuracy coefficient ≤ ±0.1% of span ≤ ±0.01% of span / °C basic values Basic Temperature Input type accuracy coefficient ≤ ±16 µA ≤ ±1.6 µA/°C ≤...
Page 13
Max. offset........... 20% of max. value Load (max.) ..........20 mA / 600 Ω / 12 VDC Load stability ..........≤ 0.01% of span / 100 Ω Current limit ..........≤ 28 mA Max. external loop supply ......29 VDC Effect of external loop supply voltage change ..........
DIP-SWITcH PROGRAmmING factory-calibrated standard ranges: Input: (channel 2, DP 3 and DP 4) Output: 0...20 mA 4...20 mA 0...10 V 2...10 V D P 1 D P 2 D P 1 D P 2 D P 1 D P 2 D P 1 D P 2 0...20 mA...
UL cONTROL DRAWING 5104QU01 Hazardous (classified) Location Nonhazardous Class I, Division 1, Group A,B,C,D Associated apparatus Class I , Zone 0 and 1, Group IIC Galvanically Isolated Class II, Division 1 Group E, F, G Intrinsically safe apparatus entity parameters: Vmax.
Page 18
Displays Programmable displays with a wide selection of inputs and outputs for display of temperature, volume and weight, etc. Feature linearisation, scaling, and difference measurement functions for programming via PReset software. Ex interfaces Interfaces for analogue and digital signals as well as HART signals between sensors / I/P converters / ®...
Need help?
Do you have a question about the 5104A and is the answer not in the manual?
Questions and answers