1.18 Test and calibration

WARNING!
The following measures must be carried out in compliance with the
accident prevention instructions. The appropriate electrical tools must be
used.
A calibration instrument, which indicates voltages, currents, and
phase angles with an error ≤ 0.1 %, is required for testing the
transducer. The output signals are measured with a digital
multimeter of the same accuracy.
If a readjustment shall be carried out, a PC with the program
"SIMEAS PAR", like for the calibration, is required in addition to
the calibration instrument.
During calibration of the DC-current-outputs the burden must not
7 5 , V
exceed a maximum output burden of R
=
.
BIN
IAN
E50417-K109U-C322-A
SIMEAS
33
1