Instructions for disassembling and reassembling the transducer systems in the threephase current servomotors 1ft603. - 1ft613. and 1fk604. - 1fk610. (12 pages)
Simeas-t series with auxiliary power for alternating voltage or alternating current rms with expanded start/end range and non-linear characteristic curve (24 pages)
Page 2
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Purpose of this documentation .................... 5 Checking the consignment ....................5 Security information ......................6 Transportation and storage ....................6 Notes on warranty ....................... 7 About Siemens' Transducers....................7 Safety notes ............................10 Preconditions for use ......................10 2.1.1 Warning symbols on device ....................10 2.1.2...
Page 4
Table of contents Connecting ............................31 Basic safety notes ......................31 4.1.1 Connect or disconnect device only in a de-energized state ..........32 Connecting note ........................ 33 Direct connection ......................34 Coaxial connection ......................35 2 Wire Extension ........................ 36 3 Terminal .........................
Introduction Purpose of this documentation These instructions are a brief summary of important features, functions and safety information, and contain all information required for safe use of the device. Read the instructions carefully prior to installation and commissioning. In order to use the device correctly, first review its principle of operation.
In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept. Siemens’ products and solutions only form one element of such a concept. Customer is responsible to prevent unauthorized access to its plants, systems, machines and networks.
The sales contract contains all obligations on the part of Siemens as well as the complete and solely applicable warranty conditions. Any statements regarding device versions described in the manual do not create new warranties or modify the existing warranty.
Page 8
Introduction 1.6 About Siemens' Transducers Maximum power is radiated axially (perpendicular) from the transducer face in a line referred to as the axis of transmission. Where power is reduced by half (– 3 dB), a conical boundary defining the sound beam, centered about the axis of transmission, is established. The diametric measurement of the cone in degrees defines the beam angle.
Page 9
Introduction 1.6 About Siemens' Transducers XPS-10, XPS-15/15F, ST-H Transducer with explosion XPS-30, XRS-5/5C proof conduit seal ① Explosion proof conduit seal ② Transducer ③ Transducer face ④ 3 db boundary ⑤ Axis of transmission Optional Perpendicular to Transducer face Note Use in hazardous areas The XPS-15F and XRS-5C already have a built-in explosion proof conduit seal.
Safety notes Preconditions for use This device left the factory in good working condition. In order to maintain this status and to ensure safe operation of the device, observe these instructions and all the specifications relevant to safety. Observe the information and symbols on the device. Do not remove any information or symbols from the device.
Safety notes 2.1 Preconditions for use 2.1.3 Improper device modifications WARNING Improper device modifications Risk to personnel, system and environment can result from modifications to the device, particularly in hazardous areas. • Only carry out modifications that are described in the instructions for the device. Failure to observe this requirement cancels the manufacturer's warranty and the product approvals.
Safety notes 2.2 Use in hazardous areas WARNING Risk of explosion If the top section separates from the main body of the transducer, live circuitry will be exposed to the hazardous environment, increasing the risk of an explosion if volatile or explosive dusts or gases are in sufficient concentration.
If you need additional information not covered by these instructions, contact your local Siemens office or company representative. Note Operation under special ambient conditions...
Refer to the information in Technical specifications (Page 38). Note Material compatibility Siemens can provide you with support concerning selection of sensor components wetted by process media. However, you are responsible for the selection of components. Siemens accepts no liability for faults or failures resulting from incompatible materials.
Page 15
Installing/mounting 3.1 Basic safety notes WARNING Exceeded maximum permissible operating pressure Risk of injury or poisoning. The maximum permissible operating pressure depends on the device version, pressure limit and temperature rating. The device can be damaged if the operating pressure is exceeded. Hot, toxic and corrosive process media could be released.
Installing/mounting 3.1 Basic safety notes 3.1.1 Installation location requirements 3.1.1.1 Insufficient air supply WARNING Insufficient air supply The device may overheat if there is an insufficient supply of air. • Install the device so that there is sufficient air supply in the room. •...
Installing/mounting 3.2 Disassembly 3.1.2 Proper mounting CAUTION Loss of type of protection Damage to device if the enclosure is open or not properly closed. The type of protection specified on the nameplate or in Technical specifications (Page 38) is no longer guaranteed. •...
Installing/mounting 3.3 Outline and Dimensions Outline and Dimensions 3.3.1 XPS Transducers ① Radiating face Dimension XPS-10 XPS-15 XPS-30 88 mm (3.4") 121 mm (4.8") 175 mm (6.9") 122 mm (4.8") 132 mm (5.2") 198 mm (7.8") to suit ANSI, DIN and JIS standards 128 mm (5.0") 138 mm (5.4") 204 mm (8.0")
Installing/mounting 3.3 Outline and Dimensions 3.3.2 XRS-5 ① Standard ② Flange (Optional) ③ Submergence Shield (Optional) Transducers Compact Operating Instructions, 09/2021, A5E43390688-AC...
① 87 mm Ø (3.4") ② 2" NPT, R 2" (BSPT), or G 2" (BSPP) mounting thread (process connection) ③ 1" NPT conduit thread Flange Adapter ① Plastic type coupling ② Siemens flange adapter Transducers Compact Operating Instructions, 09/2021, A5E43390688-AC...
Installing/mounting 3.4 Mounting Mounting Note • The transducer is to be used only in the manner outlined in this operating instructions. • Normally, the transducer requires no cleaning or maintenance. However, if performance changes are observed, immediately shut down the level measurement system and perform a thorough inspection, especially on the transducer.
Installing/mounting 3.4 Mounting 3.4.2 Liquids applications 3.4.2.1 XPS Transducers Flexible Conduit and Bracket ① Flexible conduit ④ Transducer ② Steel channel ⑤ Safety chain ③ Coupling Flexible conduit mounted transducer should not be subjected to wind, vibration, or jarring. Submersible and Plywood ①...
Page 23
Installing/mounting 3.4 Mounting ① Nipple welded to blind flange ② Optional hazardous seal Flange, gasket, and hardware supplied by customer. Note Tighten the flange bolts evenly in order to ensure a good seal between the mating flanges. CAUTION Potential performance degradation Overtightening can cause performance degradation.
Page 24
Installing/mounting 3.4 Mounting ① Optional hazardous seal ④ Gasket (customer supplied) ② Factory flanged transducer ⑤ Customer flange, flat face only ③ Bolt ⑥ Customer flanged standpipe. If a metal flange must be welded to pipe, refer to Liquid Applications - Standpipes in the Transducer Applications Manual. Transducers Compact Operating Instructions, 09/2021, A5E43390688-AC...
Installing/mounting 3.4 Mounting 3.4.2.2 XRS-5 Suspended Conduit Bracket ① Rigid metal ① Flexible conduit ② Coupling ② Steel channel ③ Transducer ③ Coupling ④ Transducer Note Flexible conduit transducer should not be subjected to wind, vibration or jarring. Transducers Compact Operating Instructions, 09/2021, A5E43390688-AC...
Page 26
Installing/mounting 3.4 Mounting Submersible Plywood ① Rigid metal ① Coupling ② Coupling ③ Submergence shield Note Submersible transducer, used in applications where flooding is possible. Plywood mounting provides excellent isolation, but must be rigid enough to avoid flexing if subjected to loading. Transducers Compact Operating Instructions, 09/2021, A5E43390688-AC...
Page 27
Installing/mounting 3.4 Mounting Blind Flange Face Flange ① Nipple welded to blind flange ① Coupling ② Coupling ② Factory flanged transducer ③ Bolt ④ Gasket (Customer supplied) ⑤ Customer flanged, flat face only ⑥ Note Tighten the flange bolts evenly in order to ensure a good seal between the mating flanges. Transducers Compact Operating Instructions, 09/2021, A5E43390688-AC...
Installing/mounting 3.4 Mounting 3.4.2.3 ST-H Non-corrosive Applications WARNING Corrosive Not suitable for use in a corrosive environment. A - Flexible Conduit B - Bracket C - Plywood D - Blind Flange Transducers Compact Operating Instructions, 09/2021, A5E43390688-AC...
Page 29
Installing/mounting 3.4 Mounting ① Flexible conduit ⑤ Plywood mounting provides excellent isolation, but must be rigid enough to avoid flexing if subjected to loading. ② Steel plate ⑥ Nipple welded to blind flange ③ Plastic type coupling ⑦ Plastic type coupling ④...
Page 30
Plastic type coupling ② Siemens flange adapter Note Flange, gasket, and hardware supplied by customer. Customer flanged standpipe. If a metal flange must be welded to pipe, refer to the Transducer Application Manual available at http://www.siemens.com/processautomation (https://w3.siemens.com/mcms/sensor-systems/en/process-instrumentation/level- measurement-with-level-measuring- instruments/continuous/ultrasonic/transducers/Pages/transducers.aspx). Coupling Coupling ①...
Connecting Basic safety notes WARNING Incorrect conduit system Risk of explosion in hazardous areas as result of open cable inlet or incorrect conduit system. • In the case of a conduit system, mount a spark barrier at a defined distance from the device input.
Connecting 4.1 Basic safety notes WARNING Improper laying of shielded cables Risk of explosion through compensating currents between hazardous area and the non-hazardous area. • Shielded cables that cross into hazardous areas should be grounded only at one end. • If grounding is required at both ends, use an equipotential bonding conductor. 4.1.1 Connect or disconnect device only in a de-energized state WARNING...
Connecting 4.2 Connecting note NOTICE Condensation in the device Damage to device through formation of condensation if the temperature difference between transportation or storage and the mounting location exceeds 20 °C (36 °F). • Before taking the device into operation let the device adapt for several hours in the new environment.
Connecting 4.3 Direct connection Direct connection ① Connection for Transducer ④ Black ② Metal conduit ⑤ White ③ Explosion proof conduit seal ⑥ Drain/shield Class I, Div. 1, Group A, B, C, D or Class II, Div. 1, Group E, F, G Safe Note When connecting to SITRANS LUT400, SITRANS LUC500, MultiRanger 100/200, or...
Connecting 4.4 Coaxial connection Coaxial connection ① Connection for Transducer ② Metal conduit ③ Explosion proof conduit seal ④ Junction box Class I, Div. 1, Group A,B,C,D or Class II, Div. 1, Group E,F,G Safe Note When connecting to SITRANS LUT400, SITRANS LUC500, MultiRanger 100/200, or HydroRanger 200, do NOT use coaxial cable.
Connecting 4.5 2 Wire Extension 2 Wire Extension ① Connection for Transducer ⑤ Junction box ② Metal conduit ⑥ Drain/shield ③ Explosion proof conduit seal ⑦ White ④ Black Class I, Div. 1, Group A,B,C,D or Class II, Div. 1, Group E,F,G Safe Note When connecting to SITRANS LUT400, SITRANS LUC500, MultiRanger 100/200, or...
Connecting 4.6 3 Terminal 3 Terminal Note For SITRANS LUT400, MultiRanger 100/200, and HydroRanger 200 only. 3 Terminal Direct ① ST-H Transducer ② Black ③ White ④ Shield 3 Terminal Extension Extend cable using 0.823 mm (18 AWG) shielded/twisted pair. Transducers Compact Operating Instructions, 09/2021, A5E43390688-AC...
Technical specifications Note Device specifications Siemens makes every attempt to ensure the accuracy of these specifications but reserves the right to change them at any time. For a complete listing, including Approvals, see the full operating instructions. Specifications Specification XRS-5/5C...
Applications Note • The transducer is to be used only in the manner outlined in this operating instructions. • Normally, the transducer requires no cleaning or maintenance. However, if performance changes are observed, immediately shut down the level measurement system and perform a thorough inspection, especially on the transducer.
Applications A.1 Liquids applications ① Blind flange ⑥ Support for standpipe in stilling well ② Stilling will with standpipe installed ⑦ Standpipe ③ Inlet from stilling well into standpipe ⑧ Transducer ④ Inlet from primary element to stilling well ⑨ TS-3 ⑤...
Standpipes Open Channel Flow Measurement In many applications, access must be made via a standpipe. In such cases, a Siemens flange adapter can be used to mate to the flanged standpipe. Another option is to hang the transducer from a blind flange, respecting chemical compatibility.
Page 43
Applications A.1 Liquids applications ① Flanged transducer ① No vessel ② No intersection ③ Vessel No additional blanking required No additional blanking required ① Nipple welded into blind flange ① Nipple welded into blind flange ② Transducer ② Transducer ③ Standpipe end cut on a 45°...
Applications A.1 Liquids applications A.1.4 Volume ① Main fill level for full calibration. Above this ⑦ Span: Corresponds to tank manufactur- level erroneous readings will result as level has er's empty level entered blanking zone. ② 'Alternate' ⑧ Rise ③ 'Preferred' ⑨...
When performing an empty or full calibration, the tank must contain its normal vapour and be at its normal temperature. 5. This seal is not supplied by Siemens. The XPS-15F and XRS-5C Series transducer comes equipped with a stainless steel coupling suitable for use in hazardous locations.
Applications A.2 Solids applications Sewage lift Solids applications A.2.1 Typical A - Transducer angled to avoid seams in bin wall and aimed at discharge in order to read bin when empty. B - Avoid intersecting bin wall seams, structural members and wall irregularities. ①...
Page 47
Applications A.2 Solids applications C - Transducer too close to material inlet. Falling material will intersect sound beam and cause erroneous readings or loss of echo. D - On fluid-like solids, aim transducer perpendicular to material surface. ① Minimal angle of repose ②...
Page 48
Applications A.2 Solids applications E - On dual discharge bins, aim each transducer at the discharge point. ① Transducer Transducers Compact Operating Instructions, 09/2021, A5E43390688-AC...
C - Transducer should be aimed away from wall projections. D - This seal is not supplied by Siemens. The XPS-15F and XRS-5C transducer comes equipped with a stainless steel coupling suitable for use in hazardous locations.
Page 50
Applications A.2 Solids applications ① Drag conveyor ② Infeed ③ Typical high level ④ Typical low level A - Transducer should be mounted perpendicular to slope of wood chips. Transducers Compact Operating Instructions, 09/2021, A5E43390688-AC...
Certificates Wiring setups for hazardous area installations Note Check the device nameplate, confirm the approval rating, and perform installation and wiring according to your local safety codes. Device nameplates XRS-5/5C XPS-10 XPS-15 XPS-30 Transducers Compact Operating Instructions, 09/2021, A5E43390688-AC...
Page 52
ST-H (ATEX/UKEX/INMETRO/CSA) (FM) The ATEX and UKEX certificates and CSA connection drawings can be downloaded from the product page of our website at: https://www.automation.siemens.com/w1/automation- technologyst- h-transducer-18736.htm (http://www.siemens.com/processinstrumentation/certificates). Go to Support > Approvals/Certificates for the ATEX and UKEX certificates. Go to Support > Installation Drawings > Level Measurement > Continuous - Ultrasonic downloading the CSA connection drawing number 1-9470004Z-DX-A.
Certificates B.2 Instructions specific to hazardous area installations Instructions specific to hazardous area installations (Reference European ATEX Directive 2014/34/EU, Annex II, 1/0/6) These following instructions apply to equipment covered by certificate numbers SIRA 99ATEX5091X (XRS-5), SIRA 99ATEX5153X (XPS), SIRA 13ATEX5017X (ST-H), CSAE 21UKEX5096X (XRS-5), CSAE 21UKEX5092X (XPS), and CSAE 21UKEX5093X (ST-H).
Page 54
Certificates B.2 Instructions specific to hazardous area installations XRS-5 XPS Transducer ST-H Temperature range -20 °C to +65 °C -40 °C to + 95 °C -20 °C to +60 °C 5. The equipment has not been assessed as a safety related device as referred to by EC Directive 2014/34/EU, Annex II, clause 1.5.
Page 55
Certificates B.2 Instructions specific to hazardous area installations Specific conditions of use The apparatus shall only be supplied from a circuit containing a suitably rated fuse having a breaking capacity of at least 1500 A. Parts of the enclosure may be non-conducting and may generate an ignition-capable level of electrostatic charge under certain extreme conditions.
Entering a serial number 1. Open the PIA Life Cycle Portal (https://www.pia-portal.automation.siemens.com). 2. Select the desired language. 3. Enter the serial number of your device. The product documentation relevant for your device is displayed and can be downloaded.
In addition to our technical support, Siemens offers comprehensive online services at Service & Support (http://www.siemens.com/automation/serviceandsupport). Contact If you have further questions about the device, contact your local Siemens representative at Personal Contact (http://www.automation.siemens.com/partner). To find the contact for your product, go to "all products and branches" and select "Products &...