Integrated Control Diagnostic Modes (Continued)
Code
Diagnostic Codes/Status of Equipment
E180
Outdoor air temperature sensor failure.
Only shown if shorted or out of range
(Communicating systems only)
E200
Hard Lock out - Rollout circuit open or
previously open
E201
Indoor blower/communication failure
- Unable to communicate with blower
motor
E202
Indoor blower motor mis-match - indoor
motor horsepower does not match unit
capacity
E203
Appliance capacity size is NOT pro-
grammed. Invalid unit codes. Refer to
configuration flow chart.
E204
Gas valve mis-wired
E205
Gas valve control relay contact shorted Check wiring on control and gas valve. If wiring is correct replace
E206
Gas valve second-stage relay failure
E207
Hot surface igniter sensed open - Refer
to troubleshooting
E223
Low pressure switch failed open
E224
Low pressure switch failed closed -Re-
fer to troubleshooting
E225
High pressure switch failed open -Refer
to troubleshooting
E226
High pressure switch failed closed
-Refer to troubleshooting
507404-04
Action Required to Clear and Recover
Compare outdoor sensor resistance to temperature resistance charts
in unit installation instructions. Replace sensor pack if necessary. At
beginning of (any) configuration, furnace or air handler control will
sense outdoor air and discharge air temperature sensor(s) If detected
(reading in range), appropriate feature will be set as installed and that
could be seen in 'About ' screen. In normal operation after control rec-
ognizes sensors, alarm will be sent if valid temperature reading is lost.
To get rid of setting and alarm, redo configuration and make sure that
temperature sensor is marked as not installed in indoor Unit 'About'
screen. When indoor unit control is replaced thermostat will 'tell' new
control if temperature sensor is in system or not. Clears 30 seconds
after fault recovered.
Correct cause of rollout trip or replace flame rollout switch. Test fur-
nace operation. Cleared after fault recovered.
Indoor blower communication failure including power outage. Lost
communication with indoor blower motor. Possible causes: motor
not powered, loose wiring. Problem may be on control or motor side.
Cleared after fault recovered.
Incorrect appliance capacity code selected. Check for proper config-
uring under Unit Size Code for Furnace/Air Hander on configuration
guide or in installation instructions. Cleared after the correct match is
detected following a reset. (Remove thermostat from system while ap-
plying power and reprogramming)
No appliance capacity code selected. Check for proper configuring
under Unit Size Codes for Furnace on configuration guide or in instal-
lation instruction. Critical Alert Cleared after valid unit code is read fol-
lowing a reset (remove thermostat from system while applying power
and reprogramming)
Check gas valve operation and wiring. Clears when repaired
control.
Furnace will operate on 1st stage for remainder of the heating de-
mand. Will clear after fault recovered. If unable to operate 2nd stage
replace control.
Measure resistance of hot surface igniter. Replace if open or not
within specified range found in 10M. Resumes normal operation after
fault is cleared.
Check pressure(inches W.C) of low pressure switch closing on heat
call. Measure operating pressure (inches w.c.). Inspect vent and
combustion air inducer for correct operation and restriction. Resumes
normal operation after fault is cleared.
Check pressure(inches W.C) of low pressure switch closing on heat
call. Measure operating pressure (inches w.c.). Inspect vent and
combustion air inducer for correct operation and restriction. Resumes
normal operation after fault is cleared.
Check pressure(inches W.C) of high pressure switch closing on heat
call. Measure operating pressure (inches w.c. Inspect vent and com-
bustion air inducer for correct operation and restriction Resumes
normal operation after fault is cleared.
Check operation of high pressure closing on heat call. Measure oper-
ating pressure (inches w.c.). Inspect vent and combustion air inducer
for correct operation and restrictio. Resumes normal operation after
fault is cleared.
Issue 1621
Page 69 of 80