Allied Air A96US2V Installation Instructions Manual page 21

Warm air gas furnace upflow/horizontal left air discharge direct vent & non-direct vent
Table of Contents

Advertisement

Maximum Allowable Exhaust Vent Lengths with Furnace Installed in a Closet or Basement Using Ventilated
Number
of 90°
Elbows
45
Used
1
66
2
61
3
56
4
51
5
46
6
41
7
36
8
31
9
26
10
21
Number
of 90°
Elbows
45
Used
1
66
2
61
3
56
4
51
5
46
6
41
7
36
8
31
9
26
10
21
* Size intake and exhaust pipe length separately. Values in table are for intake OR Exhaust, not combined total. Both Intake and Exhaust must
be same pipe size.
* Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length calculation.
507404-04
Attic or Crawl Space for Intake Air in Feet
Standard Termination at Elevation 0 - 4500 ft
2" Pipe
Model
70
90
110
135
51
29
9
n/a
46
24
4
41
19
n/a
36
14
31
9
26
4
21
n/a
16
11
6
Standard Termination at Elevation 4500 - 10,000 ft
2" Pipe
Model
70
90
110
135
51
29
n/a
n/a
46
24
41
19
36
14
31
9
26
4
21
n/a
16
11
6
2-1/2" Pipe
Model
45
70
90
110
95
95
73
38
90
90
68
33
85
85
63
28
80
80
58
23
75
75
53
18
70
70
48
13
65
65
43
8
60
60
38
3
55
55
33
n/a
50
50
28
2-1/2" Pipe
Model
45
70
90
110
95
95
73
38
90
90
68
33
85
85
63
28
80
80
58
23
75
75
53
18
70
70
48
13
65
65
43
8
60
60
38
3
55
55
33
n/a
50
50
28
Table 5C
Issue 1621
3" Pipe
Model
135
45
70
90
n/a
113
112
93
108
107
88
103
102
83
98
97
78
93
92
73
88
87
68
83
82
63
78
77
58
73
72
53
68
67
48
3" Pipe
Model
135
45
70
90
n/a
113
112
93
108
107
88
103
102
83
98
97
78
93
92
73
88
87
68
83
82
63
78
77
58
73
72
53
68
67
48
110
135
93
89
88
84
83
79
78
74
73
69
68
64
63
59
58
54
53
49
48
44
110
135
93
89
88
84
83
79
78
74
73
69
68
64
63
59
58
54
53
49
48
44
Page 21 of 80