Allied Air A96US2V Installation Instructions Manual page 19

Warm air gas furnace upflow/horizontal left air discharge direct vent & non-direct vent
Table of Contents

Advertisement

Number of
90° Elbows
Used
45
1
76
2
71
3
66
4
61
5
56
6
5
7
46
8
41
9
36
10
31
Number of
90° Elbows
Used
45
1
76
2
71
3
66
4
61
5
56
6
5
7
46
8
41
9
36
10
31
*Size intake and exhaust pipe length separately. Values in table are for intake OR Exhaust, not combined total. Both Intake and Exhaust
must be same pipe size.
507404-04
Maximum Allowable Intake or Exhaust Vent Length in Feet
Standard Termination at Elevation 0 - 4500 ft
2" Pipe
Model
70
90
110 135
61
39
19
n/a 110 110 88
56
34
14
51
29
9
46
24
n/a
41
19
36
14
31
9
26
n/a
21
16
Standard Termination Elevation 4500 - 10,000 ft
2" Pipe
Model
70
90
110 135
61
39
n/a
n/a 110 110 88
56
34
51
29
46
24
41
19
36
14
31
9
26
n/a
21
16
2-1/2" Pipe
Model
45
70
90 110 135
53
105 105 83
48
100 100 78
43
95
95
73
38
90
90
68
33
85
85
63
28
80
80
58
23
75
75
53
18
70
70
48
13
65
65
43
8
2-1/2" Pipe
Model
45
70
90 110 135
53
105 105 83
48
100 100 78
43
95
95
73
38
90
90
68
33
85
85
63
28
80
80
58
23
75
75
53
18
70
70
48
13
65
65
43
8
Table 5A
Issue 1621
3" Pipe
Model
45
70
90
n/a
133
132 113
128
127 108
123
122 103
118
117
98
113
112
93
108
107
88
103
102
83
98
97
78
93
92
73
88
87
68
3" Pipe
Model
45
70
90
n/a
133
132 113 113
128
127 108 108
123
122 103 103
118
117 98
113
112 93
108
107 88
103
102 83
98
97
78
93
92
73
88
87
68
110
135
113
109
108
104
103
99
98
94
93
89
88
84
83
79
78
74
73
69
68
64
110
135
109
104
99
98
94
93
89
88
84
83
79
78
74
73
69
68
64
Page 19 of 80