C
I
OMPLETING THE
NSTALLATION
Deciding on where to install the Air Conditioner (Continue)
MH060FXEA3B
Indoor unit
026/035/052
CAUTION:
3 m as minimum pipe length: It will reduce
noise and vibration.
This value must be increased at 7.5 meters in
case it is connected just one indoor unit.
300 mm
minimum
600 mm
minimum
Piping length and the height
Dimension
Composition
System can work with one indoor unit connected, but it is recommended that the TOTAL number
of indoor unit suggested by manufacturer are connected to obtain the maximum performance.
8
E-
FJM_IM_DB98-31792_E_6.10.10.indd 8
Power supply
Outdoor unit
Ø, V, Hz
MH060FXEA3B
1,220-240, 50
600 mm
A
minimum
300 mm
minimum
1 Room max
3 Room total max
length
length
20m
45 m
A,B,C
A+B+C
Make at least one round:
It will reduce noise and vibration
The appearance of the unit may be different from the diagram depending on the model.
Piping outside diameter
Unit
026/035
052
B
Main power switch
Max height between
Max height between
indoor unit & outdoor unit
indoor units
15m
7.5 m
(H)
(h)
Outside diameter
Liquid
Gas
3/8"
1/4"
1/2"
(h) (H)
C