Testing the drainage
Prepare a little water about 5 liter.
1
Open the cover of water supply intake by turning and pulling the cover.
(MHFEEA/NJLHXEA)
2
Pour water into the the indoor unit as shown in figure.
Note
If you do not pour water inside the water supply intake,
wateray spill from the indoor unit.
3
Confirm that the water flows out through the drain hose.
4
Reassemble the cover of water supply intake.(MHFEEA/NJLHXEA)
CAUTION
When not installing the drain pump
Do not give the hose upward gradient after the connection
port. This will cause water to flow backwards when the unit
is stopped, resulting in water leaks.
Upward gradient
Do not apply force to the piping on the unit side when
connecting the drain hose. The hose should not be allowed
to hang loose from its connection to the unit. Fasten the
hose to a wall, frame or other support as close to the unit as
possible.
Support pieces
Ceiling
FJM_IM_DB98-31792_E_7.14.10.indd 19
Ceiling
MHFEEA/NJLHXEA
MHFUEA
When installing the drain pump
When installing a flexible hose, the difference of
pivot of a drain hose port and a drain hose must
be within 20mm. If the difference of each pivot is
more than 20mm, or a flexible hose is bent
steeply, a flexible hose may leak.
20mm or more
1/100 or more
Flexible hose
Ceiling
C
I
OMPLETING THE
NSTALLATION
Water supply intake
19