Performing Leak Test & Insulation - Samsung MH080FXEA4B Installation Manual

Hide thumbs Also See for MH080FXEA4B:
Table of Contents

Advertisement

Performing leak test & insulation
Leak test
LEAK TEST WITH NITROGEN (before opening valves)

In order to detect basic refrigerant leaks, before recreating the vacuum and
recirculating the R-410A, it's responsable of installer to pressurize the whole
system with nitrogen (using a cylinder with pressure reducer)
at a pressure above 30 bar (gauge).
LEAK TEST WITH R-410A (after opening valves)

Before opening valves, discharge all the nitrogen into the system and create
vacuum. After opening valves check leaks using a leak detector for refrigerant
R-410A.
CAUTION
Discharge all the nitrogen to create a vacuum and charge
the system.
Insulation
Once you have checked that there are no leaks in the system,
you can insulate the piping and hose.
1
To avoid condensation problems, place T13.0 or thicker Acrylonitrile
Butadien Rubber separately around each refrigerant pipe.
Note
Always make the seam of pipes face upwards.
2
Wind insulating tape around the pipes and drain hose avoiding to compress
the insulation too much.
3
Finish wrapping insulating tape around the rest of the pipes leading to the
outdoor unit.
4
The pipes and electrical cables connecting the indoor unit with the outdoor
unit must be fixed to the wall with suitable ducts.
CAUTION
All refrigerant connection must be accessible, in order to permit
either unit maintenance or removing it completely.
FJM_IM_DB98-31792_E_6.10.10.indd 17
C
I
OMPLETING THE
NSTALLATION
A B
No gap
NBR(T13.0 or thicker)
Insulation cover pipe
Indoor unit
Be sure to overlap
the insulation
CAUTION
Must fit tightly against body

without any gap.
17
E-
2010-6-10 9:53:43