ELECTRICAL WIRING

13.3.4. SINGLE, TWIN, TRIPLE AND QUAD DIP SWITCH SETTING

Dip Switch Setting (No H-Link example:)
-
SINGLE

Dip switch setting (H-Link example)

-
Cycle Nº0
Cycle Nº1
Before
shipment
Name of Dip
Unit
Switch
Refrigerant
Cycle
Outdoor
Unit
End Terminal
Resistance
Refrigerant
Cycle
Indoor Unit
Indoor Unit
Address
TWIN
TRIPLE
Cycle Nº2
Cancelation
Cancelation
Setting Before
Mark
Shipment
DSW4
1 2 3 4
DSW5-1P
1 2
DSW5
1 2 3 4
RSW
Mark
DSW5 (End Terminal Resistance)
DSW4 (Refrigerant Cycle)
Outdoor Unit
Indoor Units
DSW5 (Refrigerant Cycle)
RSW (Indoor Unit Address)
For setting refrigerant cycle address of outdoor unit. Set the DSW4 not to overlap
the setting of other outdoor units in the same H-LINK system
For matching impedance of transmission circuit. Set the DSW5 according to the
quantity of outdoor units in the H-LINK system.
Setting of End Terminal Resistance
Before shipment, No.1 pin of DSW5 is set at the "ON" side.
In the case that the outdoor units quantity in the same H-link is 2 or more, set No.1
pin of DSW5 at the "OFF" side from the 2nd unit. If only one outdoor unit is used,
no setting is required.
For setting refrigerant cycle address of indoor unit. Set the DSW5 corresponding to
the address of outdoor unit in the same refrigerant cycle.
For setting indoor unit address. Set the RSW not to overlap the setting of other
indoor units in the same refrigerant cycle.
QUAD
Description
Function
PMGB0126A rev.2 - 11/2006
28