How to Programme
3-15 Reference 1 Source
Option:
Function:
[25] Analog Input X42/5
[29] Analog Input X48/2
[30] Ext. Closed Loop 1
[31] Ext. Closed Loop 2
[32] Ext. Closed Loop 3
NOTICE
This parameter cannot be adjusted while the motor is
running.
3-16 Reference 2 Source
Option:
Function:
Select the reference input to be
used for the second reference
signal. parameter 3-15 Reference 1
Source, parameter 3-16 Reference 2
Source and 3-17 Reference 3 Source
define up to 3 different reference
signals. The sum of these reference
signals defines the actual reference.
[0]
No function
[1]
Analog Input 53
[2]
Analog Input 54
[7]
Pulse input 29
[8]
Pulse input 33
[20]
Digital pot.meter
*
[21]
Analog input X30/11
[22]
Analog input X30/12
[23]
Analog Input X42/1
[24]
Analog Input X42/3
[25]
Analog Input X42/5
[29]
Analog Input X48/2
[30]
Ext. Closed Loop 1
[31]
Ext. Closed Loop 2
[32]
Ext. Closed Loop 3
NOTICE
This parameter cannot be adjusted while the motor is
running.
4-10 Motor Speed Direction
Option:
Function:
Selects the motor speed direction required.
Use this parameter to prevent unwanted
reversing.
[0]
Clockwise
Only operation in clockwise direction is
allowed.
[2]
Both
Operation in both clockwise and anti-
*
directions
clockwise direction is allowed.
VLT HVAC Drive FC 102 Operating Instructions
NOTICE
The setting in parameter 4-10 Motor Speed Direction has
impact on the Flying Start in parameter 1-73 Flying Start.
4-53 Warning Speed High
Range:
Size
related
*
NOTICE
Any changes in parameter 4-13 Motor Speed High Limit
[RPM] reset the value in parameter 4-53 Warning Speed
High to the same value as set in parameter 4-13 Motor
Speed High Limit [RPM].
If a different value is needed in parameter 4-53 Warning
Speed High, it must be set after programming of
parameter 4-13 Motor Speed High Limit [RPM]
4-56 Warning Feedback Low
Range:
-999999.999
ProcessCtrlUnit
4-57 Warning Feedback High
Range:
999999.999
ProcessCtrlUnit
4-64 Semi-Auto Bypass Set-up
Option:
[0]
Off
*
[1]
Enabled Starts the Semi-Automatic Bypass set-up and
MG11F402 - Rev. 2013-12-16
Function:
[ par.
Enter the n
value. When the motor
HIGH
4-52 -
speed exceeds this limit (n
par. 4-13
reads SPEED HIGH. The signal outputs can
RPM]
be programmed to produce a status signal
on terminal 27 or 29 and on relay output
01 or 02. Programme the upper signal
limit of the motor speed, n
normal working range of the frequency
converter.
Function:
[ -999999.999 -
Enter the lower feedback
par. 4-57
limit. When the feedback
*
ProcessCtrlUnit]
falls below this limit, the
display reads Feedb
The signal outputs can be
programmed to produce a
status signal on terminal
27 or 29 and on relay
output 01 or 02.
Function:
[ par. 4-56 -
Enter the upper feedback
999999.999
limit. When the feedback
*
ProcessCtrlUnit]
exceeds this limit, the
display reads Feedb
The signal outputs can be
programmed to produce a
status signal on terminal
27 or 29 and on relay
output 01 or 02.
Function:
No function
continue with the procedure described above.
), the display
HIGH
, within the
HIGH
6
6
.
Low
.
High
97