Digital Inputs - Danfoss vlt hvac drive fc 102 Operating Instructions Manual

110-1400 kw
Hide thumbs Also See for vlt hvac drive fc 102:
Table of Contents

Advertisement

How to Programme
5-01 Terminal 27 Mode
Option:
[0]
Input
*
[1]
Output Defines terminal 27 as a digital output.
5-02 Terminal 29 Mode
Option:
6
6
[0]
Input
*
[1]
Output Defines terminal 29 as a digital output.

6.1.4 5-1* Digital Inputs

Parameters for configuring the input functions for the
input terminals.
The digital inputs are used for selecting various functions
in the frequency converter. All digital inputs can be set to
the following functions
Digital input function
No operation
Reset
Coast inverse
Coast and reset inverse
DC-brake inverse
Stop inverse
External interlock
Start
Latched start
Reversing
Start reversing
Jog
Preset reference on
Preset ref bit 0
Preset ref bit 1
Preset ref bit 2
Freeze reference
Freeze output
Speed up
Speed down
Set-up select bit 0
Set-up select bit 1
Pulse input
Ramp bit 0
98
Function:
NOTICE
This parameter cannot be adjusted while
the motor is running.
Defines terminal 27 as a digital input.
Function:
NOTICE
This parameter cannot be adjusted while
the motor is running.
Defines terminal 29 as a digital input.
Select
Terminal
[0]
All *terminal 19, 32, 33
[1]
All
[2]
27
[3]
All
[5]
All
[6]
All
[7]
All
[8]
All *terminal 18
[9]
All
[10]
All
[11]
All
[14]
All *terminal 29
[15]
All
[16]
All
[17]
All
[18]
All
[19]
All
[20]
All
[21]
All
[22]
All
[23]
All
[24]
All
[32]
terminal 29, 33
[34]
All
VLT HVAC Drive FC 102 Operating Instructions
Digital input function
Mains failure inverse
Fire mode
Run Permissive
Hand start
Auto start
DigiPot Increase
DigiPot Decrease
DigiPot Clear
Counter A (up)
Counter A (down)
Reset Counter A
Counter B (up)
Counter B (down)
Reset Counter B
Sleep Mode
Reset Maintenance Word
PTC Card 1
Lead Pump Start
Lead Pump Alternation
Pump 1 Interlock
Pump 2 Interlock
Pump 3 Interlock
Table 6.7
5-12 Terminal 27 Digital Input
The parameter contains all options and functions listed in
parameter group except for option [32] Pulse input.
5-13 Terminal 29 Digital Input
The parameter contains all options and functions listed in
parameter group except for option [32] Pulse input.
5-14 Terminal 32 Digital Input
The parameter contains all options and functions listed in
parameter group except for option [32] Pulse input.
5-15 Terminal 33 Digital Input
The parameter contains all options and functions listed in
parameter group .
5-40 Function Relay
Array [8]
(Relay 1 [0], Relay 2 [1]
Option MCB 105: Relay 7 [6], Relay 8 [7] and Relay 9 [8]).
Select options to define the function of the relays.
The selection of each mechanical relay is realised in an array
parameter.
Option:
[0]
[1]
[2]
[3]
[4]
MG11F402 - Rev. 2013-12-16
Select
Terminal
[36]
All
[37]
All
[52]
All
[53]
All
[54]
All
[55]
All
[56]
All
[57]
All
[60]
29, 33
[61]
29, 33
[62]
All
[63]
29, 33
[64]
29, 33
[65]
All
[66]
All
[78]
All
[80]
All
[120]
All
[121]
All
[130]
All
[131]
All
[132]
All
Function:
No operation
Control Ready
Drive ready
Drive rdy/rem ctrl
Standby / no warning