Danfoss vlt hvac drive fc 102 Operating Instructions Manual page 102

110-1400 kw
Hide thumbs Also See for vlt hvac drive fc 102:
Table of Contents

Advertisement

How to Programme
6-01 Live Zero Timeout Function
Option:
6
6
[0]
Off
*
[1]
Freeze
output
[2]
Stop
[3]
Jogging
[4]
Max. speed
[5]
Stop and
trip
Par 6-xx
High Ref./
Feedb. Value'
Par 6-xx
Low Ref./
Feedb. Value'
Illustration 6.12
100
Function:
Select the time-out function. The function set
in parameter 6-01 Live Zero Timeout Function is
activated if the input signal on terminal 53 or
54 is below 50% of the value in
parameter 6-10 Terminal 53 Low Voltage,
6-12 Terminal 53 Low Current,
parameter 6-20 Terminal 54 Low Voltage or
parameter 6-22 Terminal 54 Low Current for a
time period defined in parameter 6-00 Live Zero
Timeout Time. If several time-outs occur
simultaneously, the frequency converter
prioritises the time-out functions as follows
1.
Parameter 6-01 Live Zero Timeout
Function
2.
8-04 Control Timeout Function
The output frequency of the frequency
converter can be:
[1] frozen at the present value
[2] overruled to stop
[3] overruled to jog speed
[4] overruled to max. speed
[5] overruled to stop with subsequent
trip
Ref./Feedback
[RPM]
1500
1200
900
600
300
150
1 V
5 V
Par 6-xx
'Low Voltage'or
'Low Current'
Par 6-xx
'High Voltage'or
'High Current'
VLT HVAC Drive FC 102 Operating Instructions
6-10 Terminal 53 Low Voltage
Range:
0.07 V
*
6-11 Terminal 53 High Voltage
Range:
10 V
*
- 10 V]
6-14 Terminal 53 Low Ref./Feedb. Value
Range:
0
[-999999.999 -
*
999999.999 ]
6-15 Terminal 53 High Ref./Feedb. Value
Range:
Size
related
*
6-16 Terminal 53 Filter Time Constant
Range:
0.001 s
*
10 V
[V]
Analog input
MG11F402 - Rev. 2013-12-16
Function:
[ 0 - par.
Enter the low voltage value. This analog
6-11 V]
input scaling value should correspond to
the low reference/feedback value set in
parameter 6-14 Terminal 53 Low Ref./Feedb.
Value.
Function:
[ par. 6-10
Enter the high voltage value. This analog
input scaling value should correspond to the
high reference/feedback value set in
parameter 6-15 Terminal 53 High Ref./Feedb.
Value.
Function:
Enter the analog input scaling value that
corresponds to the low voltage/low
current set in parameter 6-10 Terminal 53
Low Voltage and 6-12 Terminal 53 Low
Current.
Function:
[-999999.999 -
Enter the analog input scaling
999999.999 ]
value that corresponds to the high
voltage/high current value set in
parameter 6-11 Terminal 53 High
Voltage and 6-13 Terminal 53 High
Current.
Function:
NOTICE
[0.001 -
10 s]
This parameter cannot be adjusted
while the motor is running.
Enter the time constant. This is a first-
order digital low pass filter time constant
for suppressing electrical noise in terminal
53. A high time constant value improves
dampening but also increases the time
delay through the filter.