How to Programme
3-11 Jog Speed [Hz]
Range:
Function:
Size
[ 0 - par.
The jog speed is a fixed output speed
related
4-14 Hz]
at which the frequency converter is
*
running when the jog function is
activated.
See also 3-80 Jog Ramp Time.
3-41 Ramp 1 Ramp Up Time
Range:
Function:
Size
[ 1.00 -
Enter the ramp-up time, i.e. the
related
3600 s]
acceleration time from 0 RPM to
*
parameter 1-25 Motor Nominal Speed.
Select a ramp-up time such that the
output current does not exceed the
current limit in 4-18 Current Limit during
ramping. See ramp-down time in
parameter 3-42 Ramp 1 Ramp Down Time.
t
×
n
par .1 − 25
acc
nom
par .3 − 41 =
s
ref rpm
3-42 Ramp 1 Ramp Down Time
Range:
Function:
Size
[ 1.00 -
Enter the ramp-down time, i.e. the
related
3600 s]
deceleration time from
*
parameter 1-25 Motor Nominal Speed to 0
RPM. Select a ramp-down time such that no
over-voltage arises in the inverter due to
regenerative operation of the motor, and
such that the generated current does not
exceed the current limit set in 4-18 Current
Limit. See ramp-up time in
parameter 3-41 Ramp 1 Ramp Up Time.
t
×
n
par .1 − 25
dec
nom
par .3 − 42 =
s
ref rpm
4-11 Motor Speed Low Limit [RPM]
Range:
Function:
Size
[ 0 - par.
Enter the minimum limit for motor speed.
related
4-13
The motor speed low limit can be set to
*
RPM]
correspond to the manufacturer's
recommended minimum motor speed.
The motor speed low limit must not
exceed the setting in
parameter 4-13 Motor Speed High Limit
[RPM].
4-12 Motor Speed Low Limit [Hz]
Range:
Function:
Size
[ 0 -
Enter the minimum limit for motor speed.
related
par. 4-14
The motor speed low limit can be set to
*
Hz]
correspond to the minimum output
frequency of the motor shaft. The speed
low limit must not exceed the setting in
parameter 4-14 Motor Speed High Limit
[Hz].
VLT HVAC Drive FC 102 Operating Instructions
4-13 Motor Speed High Limit [RPM]
Range:
Size
related
*
NOTICE
Max. output frequency cannot exceed 10% of the
inverter switching frequency (parameter 14-01 Switching
Frequency).
NOTICE
Any changes in parameter 4-13 Motor Speed High Limit
[RPM] reset the value in parameter 4-53 Warning Speed
High to the same value as set in parameter 4-13 Motor
Speed High Limit [RPM].
4-14 Motor Speed High Limit [Hz]
Range:
Size
related
*
NOTICE
Max. output frequency cannot exceed 10% of the
inverter switching frequency (parameter 14-01 Switching
Frequency).
MG11F402 - Rev. 2013-12-16
Function:
[ par.
Enter the maximum limit for motor speed.
4-11 -
The motor speed high limit can be set to
60000
correspond to the manufacturer's
RPM]
maximum rated motor. The motor speed
high limit must exceed the setting in
parameter 4-11 Motor Speed Low Limit
[RPM]. Only parameter 4-11 Motor Speed
Low Limit [RPM] or parameter 4-12 Motor
Speed Low Limit [Hz] is displayed
depending on other parameters in the
Main Menu and depending on default
settings dependant on global location.
Function:
[ par.
Enter the max limit for motor speed.
4-12 -
parameter 4-14 Motor Speed High Limit [Hz]
par. 4-19
can match the manufacturer's
Hz]
recommended maximum motor speed.
The Motor Speed High Limit must exceed
the value in parameter 4-12 Motor Speed
Low Limit [Hz]. The output frequency must
not exceed 10% of the switching
frequency.