Danfoss vlt hvac drive fc 102 Operating Instructions Manual page 93

110-1400 kw
Hide thumbs Also See for vlt hvac drive fc 102:
Table of Contents

Advertisement

How to Programme
Q3-40 Fan Functions
Parameter 22-60 Broken Belt Function
Parameter 22-61 Broken Belt Torque
Parameter 22-62 Broken Belt Delay
Parameter 4-64 Semi-Auto Bypass Set-up
Parameter 1-03 Torque Characteristics
Parameter 22-22 Low Speed Detection
Parameter 22-23 No-Flow Function
Parameter 22-24 No-Flow Delay
Parameter 22-40 Minimum Run Time
Parameter 22-41 Minimum Sleep Time
Parameter 22-42 Wake-up Speed [RPM]
Parameter 22-43 Wake-up Speed [Hz]
Parameter 22-44 Wake-up Ref./FB
Difference
22-45 Setpoint Boost
22-46 Maximum Boost Time
Parameter 2-10 Brake Function
2-16 AC brake Max. Current
Parameter 2-17 Over-voltage Control
Parameter 1-73 Flying Start
Parameter 1-71 Start Delay
Parameter 1-80 Function at Stop
Parameter 2-00 DC Hold/Preheat Current
Parameter 4-10 Motor Speed Direction
Table 6.6 Q3-4 Application Settings
1-00 Configuration Mode
Option:
Function:
NOTICE
This parameter cannot be adjusted while
the motor is running.
[0] Open
Motor speed is determined by applying a speed
Loop
reference or by setting desired speed when in
Hand Mode.
Open Loop is also used if the frequency converter
is of a closed loop control system based on an
external PID controller providing a speed reference
signal as output.
[3] Closed
Motor Speed will be determined by a reference
Loop
from the built-in PID controller varying the motor
speed as of a closed loop control process (e.g.
constant pressure or flow). The PID controller must
be configured in parameter group 20-** Feedback
or via the Function Set-ups accessed by pressing
[Quick Menus].
VLT HVAC Drive FC 102 Operating Instructions
Q3-41 Pump Functions
22-20 Low Power Auto Set-up
Parameter 22-21 Low Power Detection
Parameter 22-22 Low Speed Detection
Parameter 22-23 No-Flow Function
Parameter 22-24 No-Flow Delay
Parameter 22-40 Minimum Run Time
Parameter 22-41 Minimum Sleep Time
Parameter 22-42 Wake-up Speed [RPM]
Parameter 22-43 Wake-up Speed [Hz]
Parameter 22-44 Wake-up Ref./FB Difference
22-45 Setpoint Boost
22-46 Maximum Boost Time
Parameter 22-26 Dry Pump Function
22-27 Dry Pump Delay
22-80 Flow Compensation
22-81 Square-linear Curve Approximation
22-82 Work Point Calculation
22-83 Speed at No-Flow [RPM]
22-84 Speed at No-Flow [Hz]
22-85 Speed at Design Point [RPM]
22-86 Speed at Design Point [Hz]
22-87 Pressure at No-Flow Speed
22-88 Pressure at Rated Speed
22-89 Flow at Design Point
22-90 Flow at Rated Speed
Parameter 1-03 Torque Characteristics
Parameter 1-73 Flying Start
NOTICE
When set for Closed Loop, the commands Reversing and
Start Reversing do not reverse the direction of the
motor.
1-03 Torque Characteristics
Option:
[0]
[1]
[2]
MG11F402 - Rev. 2013-12-16
Q3-42 Compressor Functions
Parameter 1-03 Torque Characteristics
Parameter 1-71 Start Delay
Parameter 22-75 Short Cycle Protection
Parameter 22-76 Interval between Starts
Parameter 22-77 Minimum Run Time
Parameter 5-01 Terminal 27 Mode
Parameter 5-02 Terminal 29 Mode
5-12 Terminal 27 Digital Input
5-13 Terminal 29 Digital Input
Parameter 5-40 Function Relay
Parameter 1-73 Flying Start
1-86 Trip Speed Low [RPM]
1-87 Trip Speed Low [Hz]
Function:
Compressor
For speed control of screw and scroll
torque
compressors. Provides a voltage which is
optimized for a constant torque load charac-
teristic of the motor in the entire range down
to 10 Hz.
Variable
For speed control of centrifugal pumps and
torque
fans. Also to be used when controlling more
than one motor from the same frequency
converter (e.g. multiple condenser fans or
cooling tower fans). Provides a voltage which
is optimised for a squared torque load
characteristic of the motor.
Auto Energy
For optimum energy efficient speed control
Optim. CT
of screw and scroll compressors. Provides a