A96UHMV090C12S BLOWER PERFORMANCE (less filter)
RIGHT SIDE RETURN AIR
HEATING BLOWER PERFORMANCE
Heating Adjust CFM Selections
Increase (+15%) Heat CFM
Increase (+7.5%) Heat CFM
Default Heat CFM
Decrease (-7.5% ) Heat CFM
Decrease (-15% ) Heat CFM
COOLING BLOWER PERFORMANCE
Cooling Adjust CFM
Selections
Increase (+10%) Cool CFM
Default Cool CFM
Decrease (-10%) Cool CFM
A96UHMV090C123 BLOWER PERFORMANCE (less filter)
SIDE RETURN AIR WITH OPTIONAL RETURN AIR BASE
ING BLOWER PERFORMANCE
Heating Adjust CFM Selections
Increase (15%) Heat CFM
Increase (+7.5%) Heat CFM
Default Heat CFM
Decrease(-7.5% ) Heat CFM
Decrease (-15% ) Heat CFM
COOLING BLOWER PERFORMANCE
Cooling Adjust CFM
Selections
Increase (+10%) Cool CFM
Default Cool CFM
Decrease (-10%) Cool CFM
The effect of static pressure is included in air volumes shown.
The following control configurations are available. See Installation Instructions for details and DIP switch settings.
Heat Modes Available (Heating Blower Performance Table):
Single stage thermostat:
- 40%, 70%. 100% input (three-stage) with time delays in-between
Two-stage thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts firing rate based on first- and second-stage cycle times
- W1 demand at 70% input, W2 demand at 100% input. No delay between stages
Cool Mode Available (Cooling Blower Performance table):
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position,
Continuous Fan speeds are approximately 38% of the same second-stage COOL speed position minimum 300 cfm.
Page 50 of 74
BLOWER DATA
40%
50%
702
792
673
757
644
723
608
676
571
630
First Stage Cool Speed-cfm
Low
Medium
Medium
Low
High
610
705
795
560
640
715
525
605
665
40%
50%
721
810
678
760
637
711
606
673
576
635
First Stage Cool Speed- cfm
Low
Medium
Medium
Low
High
605
715
810
570
660
735
530
600
670
Issue 1622
Heating Input Range and Blower Volume- CFM
60%
70%
881
971
841
926
802
880
745
814
689
747
Blower Speed Selections
Second Stage Cool Speed-cfm
High
Low
(Default)
920
840
810
770
725
695
Heating Input Range and Blower Volume - CFM
60%
70%
899
988
842
923
784
858
740
806
695
754
Blower Speed Selections
Second Stage Cool Speed-cfm
High
Low
(Default)
930
850
820
775
725
710
80%
90%
100%
1061
1150
1240
1010
1094
1178
959
1037
1116
882
951
1020
806
864
923
Medium
Medium
High
Low
High
(Default)
1015
1165
1300
910
1050
1190
795
945
1110
RIGHT
HEAT-
80%
90%
100%
1076
1165
1254
1004
1085
1167
932
1005
1079
873
939
1006
814
873
933
Medium
Medium
High
Low
High
(Default)
995
1165
1305
905
1050
1205
800
945
1070
507028-03