Condensate Drain - Carrier 58MXA Installation, Start-Up, And Operating Instructions Manual

Deluxe 4–way multipoise fixed-capacity direct-vent condensing gas furnace
Table of Contents

Advertisement

MAINTAIN 12 IN.
(18 IN. FOR CANADA)
MINIMUM CLEARANCE
ABOVE HIGHEST
ANTICIPATED SNOW
LEVEL. MAXIMUM OF
24 IN. ABOVE ROOF.
Fig. 31—Concentric Vent and Combustion-Air Roof
Termination (Preferred)
OVERHANG OR ROOF
12" MINIMUM
VENT
90°
BRACKET
COMBUSTION-AIR
Fig. 33—Sidewall Termination of 12 in. or More
or breach vent 58MXA furnaces. When 2 or more 58MXA
furnaces are vented near each other, 2 vent terminations may be
installed as shown in Fig. 35, 36, 37, 38, or 39, but next vent
termination must be at least 36 in. away from first 2 terminations.
It is important that vent terminations be made as shown to avoid
recirculation of flue gases. Dimension "A" in Fig. 35, 36, 37, 38,
and 39 represents distance between pipes or rain shields, as
touching or 2-in. maximum separation.
VENT
COMBUSTION
AIR
A93054
12 IN. SEPARATION
BETWEEN BOTTOM OF
COMBUSTION AIR AND
BOTTOM OF VENT
MAINTAIN 12 IN.
CLEARANCE
ABOVE HIGHEST
ANTICIPATED SNOW
LEVEL OR GRADE,
WHICHEVER IS
GREATER.
A87225
Fig. 32—Concentric Vent and Combustion-Air Side
Termination
OVERHANG OR ROOF
VENT
90°
BRACKET
COUPLING
COMBUSTION-AIR
(ELBOW PARALLEL
TO WALL)
Fig. 34—Sidewall Termination of Less than 12 in.
Unit must not be installed, operated, and then turned off and
left in an unoccupied structure during cold weather when
temperature drops to 32°F and below unless drain trap and
drain line have adequate freeze protection. See Service and
Maintenance Instructions for winterizing procedure.
Step 10—Condensate Drain
GENERAL
Condensate trap is shipped installed in the blower shelf and factory
connected for UPFLOW applies Condensate trap must be RELO-
CATED for use in DOWNFLOW and HORIZONTAL applica-
tions.
Condensate trap MUST be used for all applications.
An external trap is not required when connecting the field drain to
this condensate trap.
30
OVERHANG OR ROOF
12" MINIMUM
1" MAXIMUM
COMBUSTION-AIR
VENT
MAINTAIN 12 IN.
CLEARANCE
ABOVE HIGHEST
ANTICIPATED SNOW
LEVEL OR GRADE,
WHICHEVER IS
GREATER.
12" MINIMUM
12 IN. SEPARATION
BETWEEN BOTTOM OF
COMBUSTION AIR AND
BOTTOM OF VENT
MAINTAIN 12 IN.
CLEARANCE
ABOVE HIGHEST
ANTICIPATED SNOW
LEVEL OR GRADE,
WHICHEVER IS
GREATER.
A93055
A87226