Carrier FA4ANF Service Manual page 24

Residential fan coil units
Table of Contents

Advertisement

SIZE FEMALE
SIZE MALE
M2
T3
T2
SEC1
0.250 X 0.032
SEC2
HUM1
HUM2
AUX1
AUX2
M1
0.187 X 0.032
T1
RED
Table 4—Connections on Single Barrier Strip Mounted, Cross Slotted, Captive Binding Head (FK4B)
SCREW
TERMINAL
W2
Connection for W2 signal from thermostat
W3
Connection for W3 signal from outdoor thermostat
E
Connection for E signal from thermostat
Y/Y2
Connection for Y signal from thermostat
G
Connection for G signal from thermostat
O
Connection for O signal from thermostat
This connection is a field termination for use in connecting L lines of thermostat and outdoor unit together. There is no
L
connection of this terminal with control circuity.
Y1
Connection for low-speed compressor operation
R
Connection for R signal to thermostat (24 vac)
C
Connection for C terminal to thermostat (24 vac common)
TYPE
CONNECTION
Heater
Connection
ICM2 Motor
AC/HP CFM ADJUST
Select low, medium, or high airflow. To provide any of these
airflows, AC/HP ADJUST select must be moved to MED position.
The factory selection is LO. The adjust selections HI/LO will
regulate airflow supplied for all operational modes, except non-
heat pump heating modes, +10 percent and -10 percent respec-
tively. The adjust selection options are provided to adjust airflow
supplied to meet individual installation needs for such things as
noise, comfort, and humidity removal. (See Fig. 16.)
Table 3—Male/Female Quick-Connect Terminals (FK4B)
Motor line voltage connection (230 vac 60 Hz)
Transformer line voltage connection (230 vac 60 Hz)
Transformer tap storage terminal for 208-vac lead
Secondary connection from transformer (24 vac)
This connection is common to chassis ground through eyelet marked GROUND SCREW REQUIRED.
Secondary connection from transformer (24 vac)
Low voltage ground for humidifier option (24 vdc)
Low voltage output for humidifier option (24 vdc)
Low voltage ground for auxiliary option (24 vdc)
Low voltage output for auxiliary option (24 vdc)
Common connection to blower motor
Common connection for transformer
Common to R screw terminal and SEC2
Table 5—Connections and Connector (FK4B)
TYPE
PIN NO.
CONNECTOR
Pin 1
Pin 2
Pin 3
Pin 4
Pin 5
Pin 6
12-Pin
Pin 7
Pin 8
Pin 9
Pin 10
Pin 11
Pin 12
Pin 1
Pin 2
Pin 3
7-Pin Header
Pin 4
Pin 5
Pin 6
Pin 7
DESCRIPTION
DESCRIPTION
DESCRIPTION
Common to E screw terminal
Common to W2 screw terminal
Common to C screw terminal, SEC1 terminal, and chassis ground
Common to C screw terminal, SEC1 terminal, and chassis ground
No connection
Common to W3 screw terminal
Common to M2 and T3 quick-connects, 230 vac input
No connection
Common to M1 and T1 quick-connects, 230 vac input
No connection
No connection
No connection
Diode OR output of E or W3 or W2 thermostat signals
Thermostat G signal
Common to C, SEC1, and chassis ground
Common to C, SEC1, and chassis ground
Common to R and SEC2 (via 5-amp fuse)
Thermostat Y/Y2 signal
Thermostat Y1 signal
AC/HP TIME DELAY
Select desired time delay profile. Four motor operation delay
profiles are provided to customize and enhance system operation.
(See Fig. 16.) The selection options are:
1. The standard 90 sec off delay (factory setting).
2. No delay option used for servicing unit or when a thermostat
is utilized to perform delay functions.
3. A 30 sec on/90 sec off delay profile used when it is desirable
to allow system coils time to heat up/cool down prior to
24