Purging the indoor unit

The indoor unit is supplied with inert gas (nitrogen).
If this one isn't true, DO NOT INSTALL THE UNIT since leakage could be inside the indoor unit.
1. Unscrew the caps at the end of each pipe.
All inert gas exhausts from the indoor unit.
• To prevent dirt or foreign substances from getting into the pipes during
installation, do NOT remove the caps completely until you are ready to
connect the pipes.
• The remaining air in the Refrigeration cycle, which contains moisture,
may cause malfunction on the compressor.
• Always contact the service center or a professional installation agency
for product installation.

Cutting or extending the pipe

The length of the pipe can be:
x E
e t
d n
d e
u
t p
: o
e s
t e
S
o h
t r
n e
p u
o t
s :
e e
a p
e g
If you need a pipe longer than 5 meters:
• You must extend the assembly cable.
• You must add refrigerant to the pipes; otherwise, the indoor unit may freeze.
1.
2. If you want to shorten the pipe, cut it using a pipe cutter, ensuring that the cut edge remains at 90° with the side of the
pipe (see below examples of correct and incorrect cut edges).
Pipe
cutter
Pipe
3. To prevent a gas leak, remove all burrs at the cut edge of the pipe using a reamer.
• Face the pipe down while removing the burrs to make sure that burrs do not get in to the pipe.
4.
Pipe
Flare
MAX_XSA_IBIM_DB98-33747A_E.pdf
b a
e l
a p
e g
0 3
0 3
Oblique
90°± 2°
B
R 0.4~0.8
Pipes
Rough
Burr
Outer Diameter (D)
Depth (A)
ø6.35 mm
1.3 mm
ø9.52 mm
1.8 mm
ø12.70 mm
2.0 mm
ø15.88 mm
2.2 mm
Unscrew the caps
Flaring Size (B)
8.7 - 9.1 mm
12.8 - 13.2 mm
16.2 - 16.6 mm
19.3 - 19.7 mm