CONTROL BOARD TIMERS

The ice machine is locked into the freeze cycle for 6
minutes before a harvest cycle can be initiated.
The freeze time lock in feature is bypassed on the
initial cycle (manual start or after a full bin/safety limit
condition).
If the harvest float switch is in the down position for
10 continuous seconds during the start of a freeze
cycle, a harvest sequence is initiated.
The maximum freeze time is 45 minutes at which
time the control board automatically initiates a
harvest sequence.
The maximum harvest time is a total of 7 minutes.
If the bin switch does not activate within 3.5 minutes,
the harvest cycle extends another 3.5 minutes. If 7
minutes is exceeded a Harvest Assist Cycle starts.
The water fill valve is de-energized 1 minute after the
freeze cycle starts. The control board will energize the
water inlet valve one more times 3 minutes into the
freeze cycle.
Control boards with firmware version 2.58 or larger
The control board will stop the ice machine for 25
seconds during the freeze cycle and then re-energize.