5 HS-NCM Configuration
HS-NCM configuration changes are made via the VeriFire Tools Programming Utility, version 5.7 or higher.
VeriFire Tools can be connected to the HS-NCM via two different methods:
• VeriFire Tools connected to any node on a network using the HS-NCM for network communication.
• HS-NCM directly connected to VeriFire Tools.
NOTE: When directly connecting VeriFire Tools to the HS-NCM, if power is not being provided
via the NUP connection at the fire panel, external power is needed. Refer to "External Power for
HS-NCM Applications" on page 12
Perform the following steps to modify the HS-NCM's configuration parameters using VeriFire Tools. Refer to the
VeriFire Tools CD on-line help file.
1.
Connect the HS-NCM to the FACP via either NUP port or provide power from an external UL/ULC listed power
source.
2.
Connect VeriFire Tools to the network or directly connected to the HS-NCM.
3.
In VeriFire Tools, access the Upload/Download Screen:
4.
In the "Network Node Session" of the Upload/Download screen, find the node connected to the HS-NCM being
configured.
NOTE: When the HS-NCM is directly connected to the VeriFire Tools, the node listed in the
"Network Node Session" of the VeriFire Tools Upload/Download screen is shown as "Local
VeriFire"
5.
Double click the node to log in to the panel.
6.
Using the mouse, right click on the node connected to the HS-NCM being configured. A menu of available options is
displayed.
HS-NCM Installation Document — P/N 54014:B2 04/25/2014