Communication Circuit
TB4 (Ch A - Wire Only)
TB5 (Ch B - Wire Only)
J6 (NUP)
J7 (NUP)
J13 (USBA)
J14 (USBB)
Table 1 Voltage and Current Ratings for Communication Circuits
NOTE: For use with the NFS-640, NFS2-640, NFS-320, NFS-3030, NFS2-3030, DVC-EM, NCA-2, and
NCA, the HS-NCM must be connected via the NUP Ports!
2 The Network Communications Module for Wire
•
Supports twisted-pair wire medium.
•
NFPA Style 4 (Class B) operation or NFPA Style 7
(Class A) operation.
•
Transformer coupling provides electrical isolation
between nodes.
•
Pluggable terminal wiring with strain relief.
•
Pluggable service connector (feeds signal directly
through) in the event that power must be removed from
a node (HS-NBB).
•
Data is regenerated at each node.
•
Two network ports to allow simultaneous connection
of up to two fire alarm control panels and a
programming computer.
•
Enables software and database upload/download over
High-Speed Noti•Fire•Net.
2
Voltage and Current Rating/Protocol
10 VDC, 25mA
10 VDC, 25mA
232 Protocol
232 Protocol
Standard Protocol
Standard Protocol
Channel A
Connection
Ground Fault
Detection
Switches
S1=CH. A
S2=CH. B
Figure 1 HS-NCM-W
HS-NCM Installation Document — P/N 54014:B2 04/25/2014
(HS-NCM-W)
Channel B
Connection
USB
Connections
NUP
Ports
External
Power
Connection