Installation of indoor unit
Boring a wall hole and installing wall embedded pipe
For walls containing metal frame or metal board ,be sure to use a wall embedded
pipe and wall cover in the feed-through hole to prevent water leakage.
Be sure to caulk the gaps around the pipes with caulking material to prevent
water leakage.
1)Bore a feed-through hole of 2 1/6 in (55 mm) in the wall so it has a down slope
toward the outside.
2)Insert a wall pipe into the hole.
3)Insert a wall cover into wall pipe .
4)After completing refrigerant piping, wiring, and drain piping, caulk pipe hole gap
with putty.

Drain piping

1)Use commercial regid polyvinyl chloride pipe general VP 20 pipe, outer diameter 1 in (26 mm), inner diameter
4/5 in (20 mm) for the drain pipe.
2)The drain hose (outer diameter 5/7 in (18 mm) at connecting end, 8 2/3 in (220 mm) long)is supplied with the indoor
unit. Prepare the drain pipe picture below position.
3)The drain pipe should be inclined downward so that water will flow smoothly without any accumulation.(Should not
be trap.)
4)Insert the drain hose to this depth so it won't be pulled out of the drain pipe.
5)Insulate the indoor drain pipe with 10mm or more of insulation material to prevent condensation.
6)Remove the air filters and pour some water into the drain pan to check the water flows smoothly.
4 in (100 mm)
19
6 in (150 mm)
Drain hose
Reducer
Specifications are subject to change without notice.
Wall embedded pipe
(field supply)
Wall hole cover
2 in (50 mm)
or more
Vinyl chloride
drain pipe
INSTALLATION INSTRUCTIONS
Inside
Outside
Caulking
2 1/6 in (55 mm)
Wall embedded pipe
(field supply)
Must be no trap
Do not touch water
421 02 9260 00