Vent-Axia VA140/150KP Installation And Wiring Instructions page 6

Range axial kitchen fans

Advertisement

Fig. 5.
VA140/ 150KHP Humidity Model.
Humidity Set-Point Adjustment.
The Fan's Humidity Set-Point is factory set to switch the fan on at approximately 72%RH. The sensitivity may be
adjusted at installation from 65%RH-90%RH, by altering the adjuster on the Fan PCB.
Before adjusting the Set-Point, switch off the Mains Supply.
1. Remove the Indoor Grille [A]. Loosen the screw (top middle) of the Grille, to release front grille gently lever the
Grille downwards away from the Inner Cover [B].
2. Remove Inner Cover [B]. Loosen the screw (bottom middle) and release the inner grille gently from the Base
Housing [D].
3. To LOWER the Set-Point, turn the adjuster ANTI-CLOCKWISE. This makes the fan more sensitive to RH%, i.e.
the fan will come on at a lower RH%.
4. To RAISE the Set-Point, turn the adjuster CLOCKWISE. This makes the fan less sensitive to RH%,
i.e. the fan will come on at a higher RH%.
5. Replace the Inner Cover and Indoor Grille.
6. Reconnect the mains supply.
(If remote override is required refer to Fig 6 for installation. The remote switch will switch between automatic
humidity control and manual override. Ignore the timer control potentiometer in the diagram)
Fig. 6.
VA140/ 150KHT Humidity Timer Model.
1 Phase Supply
(220-240V 50Hz).
~
N
E
N
~
FUSE
L
Switched
Fused Spur
Fan
L
N
LS
6
Fan
L N
Humidity
Adjuster.
Timer Adjuster.