Goodman PC Installation Instructions Manual

Goodman PC Installation Instructions Manual

“m” series
Table of Contents

Advertisement

Prior to installation, thoroughly familiarize yourself with this Installation Manual. Observe all safety warnings. During
It is your responsibility to install the product safely and to educate the customer on its safe use.
These installation instructions cover the outdoor
installation of self contained package air conditioners
and heating units. See the Specification Sheets
applicable to your model for information regarding
accessories.
IO-394
8/10
I
NSTALLATION
F
S
-C
OR
ELF
H
EAT
*PC/*PH15 "M" SERIES
Affix this manual and Users Information Manual adjacent to the unit.
RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.
ATTENTION INSTALLING PERSONNEL
installation or repair, caution is to be observed.
Goodman Manufacturing Company, L.P.
5151 San Felipe, Suite 500, Houston, TX 77056
www.goodmanmfg.com
© 2010 Goodman Manufacturing Company, L.P.
I
NSTRUCTIONS
P
ONTAINED
P
U
UMP
NITS
*NOTE: Please contact your distributor or our
Specification Sheets referred to in this manual.
www.amana-hac.com
ACKAGE
website for the applicable

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PC and is the answer not in the manual?

Questions and answers

Summary of Contents for Goodman PC

  • Page 1 See the Specification Sheets Specification Sheets referred to in this manual. applicable to your model for information regarding accessories. Goodman Manufacturing Company, L.P. 5151 San Felipe, Suite 500, Houston, TX 77056 IO-394 www.goodmanmfg.com www.amana-hac.com 8/10 © 2010 Goodman Manufacturing Company, L.P.
  • Page 2: Table Of Contents

    INDEX .............................. 4 O THE NSTALLER ..............4 MPORTANT OTE TO THE OMEOWNER EGARDING RODUCT ARRANTY SHIPPING INSPECTION ..............................4 REPLACEMENT PARTS ............................... 4 .............................. 4 RDERING ARTS SAFETY INSTRUCTIONS ..............................4 CODES AND REGULATIONS ............................... 5 EPA R ............................5 EGULATIONS ...............................
  • Page 3 APH D ..........................12 WITCH UNCTIONS APH CFM D ......................12 ELIVERY AND DJUSTMENTS APH T “F ” M ......................12 HERMOSTAT APH H ..........................12 UMIDITY ONTROL APH T ..........................12 TAGE EATING APH T ..........................12 HERMOSTAT IRING (TXV) S ........................
  • Page 4: T O The Installer

    (877- damage. 254-4729) to obtain a copy. To receive the 10-year Parts Limited Warranty for Goodman branded products, online registration must be completed within 60 days of installation. Online registration is not required in California or Quebec.
  • Page 5: Codes And Regulations

    PRE-INSTALLATION CHECKS Before attempting any installation, the following points should be considered: • Structural strength of supporting members • Clearances and provision for servicing • Power supply and wiring • Air duct connections • Drain facilities and connections • Location may be on any four sides of a home, manufactured or modular, to minimize noise LEARANCES AND CCESSIBILITY...
  • Page 6: Roof Top Pre -Installation Details

    NSTALLATIONS NOTE: Sufficient structural support must be determined prior to locating and mounting the curb and package unit. Curb insulation, cant strips, flashing and general roofing material are furnished by the contractor. Curbing must be installed in compliance with the National Roofing Contractors Association Manual.
  • Page 7: Circulating Air And Filters

    If needed, these kits may be ordered through convenient access to the filters for periodic inspection and Goodman’s Service Parts department. cleaning. When installing filters, ensure the air flow arrows on the filter are pointing toward the circulator blower.
  • Page 8: Piping

    PIPING OLTAGE IRING • Heat Pumps. Connect 24V wires from the thermostat to the corresponding wires in the control box using No. 18 ONDENSATE RAIN AWG as follows: The condensate drain connection of the evaporator is a half coupling of ¾” N.P.T. A trap must be provided to have proper GPC15 24 -60 condensate drainage.
  • Page 9: Startup, Adjustments, And Checks

    STARTUP, ADJUSTMENTS, AND CHECKS 6. If unit operates properly in the heating cycle, raise the temperature setting until the heating second stage makes contact. Supplemental resistance heat, if installed should now come on. Ensure all heaters energize. NOTE: *PH1542-60 have two stages of compressor heat. During resistance heat test, increase temperature setting until third stage heat is energized.
  • Page 10: Compressor

    Compressor The following figures show a schematic of a heat pump on This item is activated by the contactor for heating and cooling, the cooling cycle and the heating cycle. In addition to a except during emergency heat. It is protected by an internal reversing valve, a heat pump is equipped with an expansion overload.
  • Page 11: Defrost Control

    C O O LIN G S E RV IC E P O RT R E V E RS IN G V A LV E S E RV IC E VA LV E S E R V IC E P O R T A C C U M U LA TO R C O M P R E S S O R D IS T RIB U TO R...
  • Page 12: Air Flow Measurement And Adjustment

    APH D IR FLOW EASUREMENT AND DJUSTMENT WITCH UNCTIONS Please review the Duct Work section before proceeding The ECM motor has an electronic control that contains eight with the airflow measurements and adjustments in this (8) 2-position dip switches. The function of these dip switches section.
  • Page 13: Expansion Valve (Txv) System

    SATURATED SUCTION PRESSURE a. If subcooling and superheat are low, adjust TXV to 15 - 18ºF then check subcooling. TEMPERATURE CHART b. If subcooling is low and superheat is high, add charge Suction Saturated Suction to raise subcooling to 10 ± 2ºF then check superheat. Pressure Temperature °F c.
  • Page 14: Heat Pump - Heating Cycle

    After superheat is adjusted it is recommended to check unit sub-cooling at the condenser coil liquid line out. In most operating conditions 10 - 15ºF of sub-cooling is adequate. EATING YCLE The proper method of charging a heat pump in the heat mode is by weighing the charge according to the total charge listed on the rating plate.
  • Page 15: Maintenance

    MAINTENANCE UTSIDE IR INTO ETURN Do not introduce cold outside air into the return duct of a heat pump installation. Do not allow air entering the indoor coil to drop The Self Contained Package Air Conditioner and Heat Pump below 65°F. Air below this temperature will cause low discharge should operate for many years without excessive service calls pressure, thus low suction pressure, and excessive defrost cy- if the unit is installed properly.
  • Page 16: Appendix

    APPENDIX...
  • Page 17: Troubleshooting Chart

    TROUBLESHOOTING CHART HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. POSSIBLE CAUSE REMEDY SYMPTOM High head - low suction a.
  • Page 18: Gph15 Blower Performance Data

    GPH15 BLOWER PERFORMANCE DATA E.S.P (In. of H Model Speed Volts CF M T1 (G) WATTS CF M T2 / T3 (W2) WATTS CF M 1058 1012 T4 / T5 (Y) WATTS CF M T1 (G) WATTS CF M 1132 1070 1011 T2 / T3...
  • Page 19 GPH15 BLOWER PERFORMANCE DATA E.S.P (In. of H Model Speed Volts 1199 1138 1085 1017 T1 (G) WATTS 1359 1322 1262 1214 1165 1119 1080 1039 T2 (Y) / T3 (W2) WATTS 1598 1559 1525 1483 1441 1398 1353 1314 T4 / T5 (HS) WATTS...
  • Page 20: Gpc15 Blower Performance Data

    GPC15 BLOWER PERFORMANCE DATA E.S.P (In. of H Model Speed Vo lts T1 (G) WATTS T2 / T3 WATTS 1058 1012 T4 / T5 WATTS T1 (G) WATTS 1132 1070 1011 T2 / T3 WATTS 1287 1236 1165 1123 1066 1012 T4 / T5 WATTS...
  • Page 21: Aph15 Blower Performance Data

    APH15 BLOWER PERFORMANCE DATA APH1524M41 APH1530M41 Cooling/HP Adjust Electric Adjust Cooling/HP Adjust Electric Adjust CFM* C FM* CFM* CFM* Speed Heat Speed Heat Minus Minus Minus Minus Normal Normal Normal N ormal Plus Plus Plus Plus Minus Minus Minus Minus Normal Normal Normal...
  • Page 22: Utput And Dip Switch Settings

    APH15 CFM OUTPUT AND DIP SWITCH SETTINGS CFM Output for DIP Switch Combinations 1-2 CFM Output for DIP Switch Combinations 5-6 (Electric Heat) (Cooling/Heating). SPEED SWITCH SWITCH ELECTRIC SPEED SWITCH SWITCH COOLING/HP MODEL MODEL HEAT (CFM) 1050 1050 APH1524 APH1524 1250 1250 1100...
  • Page 23 THIS PAGE LEFT INTENTIONALLY BLANK...
  • Page 24 Goodman Manufacturing Company, L.P. 5151 San Felipe, Suite 500, Houston, TX 77056 www.goodmanmfg.com www.amana-hac.com © 2010 Goodman Manufacturing Company, L.P.

This manual is also suitable for:

Ph15