CONDENSING UNIT
HEAT PUMP
INSTALLATION & SERVICE REFERENCE
Important Safety Instructions
The following symbols and labels are used throughout this
manual to indicate immediate or potential safety hazards. It is
the owner's and installer's responsibility to read and comply
with all safety information and instructions accompanying these
symbols. Failure to heed safety information increases the risk
of personal injury, property damage, and/or product damage.
Only personnel that have been trained to install, adjust, service or
repair (hereinafter, "service") the equipment specified in this manual
should service the equipment. The manufacturer will not be
responsible for any injury or property damage arising from improper
service or service procedures. If you service this unit, you assume
responsibility for any injury or property damage which may result. In
addition, in jurisdictions that require one or more licenses to service
the equipment specified in this manual, only licensed personnel
should service the equipment. Improper installation, adjustment,
servicing or repair of the equipment specified in this manual, or
attempting to install, adjust, service or repair the equipment specified
in this manual without proper training may result in product damage,
property damage, personal injury or death.
Cancer and Reproductive Harm
www.P65Warnings.ca.gov
HIGH VOLTAGE!
Disconnect ALL power before servicing.
Multiple power sources may be present.
Failure to do so may cause property damage,
personal injury or death.
CAUTION
Scroll equipped units should never be used to evacuate
the air conditioning system. Vacuums this low can cause
internal electrical arcing resulting in a damaged or failed
compressor.
© 2016-2019 Goodman Manufacturing Company, L.P.
19001 Kermier Rd., Waller, TX 77484
www.goodmanmfg.com
P/N: IOG-4002C Date: October 2019
Shipping Inspection
Always keep the unit upright; laying the unit on its side or top
may cause equipment damage. Shipping damage, and subse-
quent investigation is the responsibility of the carrier. Verify
the model number, specifications, electrical characteristics,
and accessories are correct prior to installation. The distribu-
tor or manufacturer will not accept claims from dealers for trans-
portation damage or installation of incorrectly shipped units.
Codes & Regulations
This product is designed and manufactured to comply with
national codes. Installation in accordance with such codes and/
or prevailing local codes/regulations is the responsibility of the
installer. The manufacturer assumes no responsibility for equip-
ment installed in violation of any codes or regulations. Rated
performance is achieved after 20 hours of operation. Rated per-
formance is delivered at the specified airflow. See outdoor unit
specification sheet for split system models or product specifi-
cation sheet for packaged and light commercial models. Speci-
fication sheets can be found at www.goodmanmfg.com for
Goodman
brand products. Within either website, please select the resi-
dential or commercial products menu and then select the
submenu for the type of product to be installed, such as air
conditioners or heat pumps, to access a list of product pages
that each contain links to that model's specification sheet.
The United States Environmental Protection Agency (EPA)
-
has issued various regulations regarding the introduc-
tion and disposal of refrigerants. Failure to follow these
regulations may harm the environment and can lead to
the imposition of substantial fines. Should you have any
questions please contact the local office of the EPA.
If replacing a condensing unit or air handler, the system must
be manufacturer approved and Air Conditioning, Heating and
Refrigeration Institute (AHRI) matched. NOTE: Installation of
unmatched systems is not allowed.
Outdoor units are approved for operation above 55°F in cooling
mode. Operation below 55°F requires the use of an approved
low ambient kit. Note: LAKT01 Low ambient kit cannot be used
with outdoor units containing ECM motors.
Damage to the unit caused by operating the unit in a structure
that is not complete (either as part of new construction or reno-
vation) is not covered under the warranty.
®
brand products or www.amana-hac.com for Amana
®

Advertisement

Table of Contents
loading

Summary of Contents for Goodman GSZ16

  • Page 1 © 2016-2019 Goodman Manufacturing Company, L.P. CONDENSING UNIT 19001 Kermier Rd., Waller, TX 77484 www.goodmanmfg.com HEAT PUMP P/N: IOG-4002C Date: October 2019 INSTALLATION & SERVICE REFERENCE Shipping Inspection Important Safety Instructions Always keep the unit upright; laying the unit on its side or top The following symbols and labels are used throughout this may cause equipment damage.
  • Page 2: Installation Clearances

    the unit can vibrate during operation, sound vibration transmis- Installation Clearances sion should be considered when installing the unit. Vibration Special consideration must be given to location of the con- absorbing pads or springs can be installed between the con- densing unit(s) in regard to structures, obstructions, other units, densing unit legs or frame and the roof mounting assembly to and any/all other factors that may interfere with air circulation.
  • Page 3: Burying Refrigerant Lines

    To avoid possible explosion, use only returnable (not disposable) service cylinders when removing refrigerant from a system. • Ensure the cylinder is free of damage which could lead to a leak or explosion. • Ensure the hydrostatic test date does not exceed 5 years. •...
  • Page 4: Refrigerant Line Connections

    Refrigerant Line Connections Leak Testing (Nitrogen or Nitrogen-Traced) IMPORTANT WARNING To avoid overheating the service valve, TXV valve, or filter To avoid the risk of fire or explosion, never use drier while brazing, wrap the component with a wet rag, or oxygen, high pressure air or flammable gases for leak use a thermal heat trap compound.
  • Page 5: High Voltage

    The condensing unit rating plate lists pertinent electrical data necessary for proper electrical service and overcurrent protec- 5000 tion. Wires should be sized to limit voltage drop to 2% (max.) 4500 from the main breaker or fuse panel to the condensing unit. 4000 Consult the NEC, CEC, and all local codes to determine the correct wire gauge and length.
  • Page 6: System Start-Up

    Open the suction service valve first! If the liquid service valve is opened first, oil from the compressor may be drawn into the NOTES: COLOR CODES indoor coil TXV, restricting refrigerant flow and affecting opera- 1) TERMINAL BLOCK MARKINGS ARE FOR GOODMAN/AMANA BL-- BLUE AIR HANDLERS. BL/PK--BLUE/PINK STRIPE BR--BROWN tion of the system.
  • Page 7: Charge Verification

    1. Break vacuum by fully opening liquid and suction base Final Charge Adjustment valves. The outdoor temperature must be 60°F or higher. Set the room 2. Set thermostat to call for cooling. Check indoor and out- thermostat to COOL, fan switch to AUTO, and set the tem- door fan operation and allow system to stabilize for 10 perature control well below room temperature.
  • Page 8 SATURATED SUCTION PRESSURE SATURATED LIQUID PR ESSU RE TEMPER ATU RE CHART TEMPER ATU RE CHART SATU RATED SUCTION SATURATED LIQUID SUC TION PRESSU RE LIQUID PRESSURE TEMPERATURE ºF TEMPERATURE ºF PSIG R-22 R-410A PSIG R-22 R-410A NOTE: SPECIFICATIONS AND PERFORMANCE DATA LISTED HEREIN ARE SUBJECT TO CHANGE WITHOUT NOTICE.
  • Page 9: Fixed Orifice

    2. The difference between the measured saturated suction Fixed Orifice temperature and the suction line temperature is the Su- 1. Temporarily install a thermometer 4-6" from the compres- perheat value. sor on the suction line. Ensure the thermometer makes 3. TXV-based systems should have a Superheat value of adequate contact and is insulated for best possible read- 8°F +/- 1°F.
  • Page 10: Troubleshooting Information

    Troubleshooting Information System Complaint No Cooling Unsatisfactory Cooling/Heating Operating Pressures POSSIBLE CAUSE Test Method DOTS IN ANALYSIS Remedy GUIDE INDICATE "POSSIBLE CAUSE" • Power Failure Test Voltage • • • Blown Fuse Inspect Fuse Size & Type • • • Unbalanced Power, 3PH Test Voltage •...
  • Page 11: Split Systems

    SPLIT SYSTEMS AIR CONDITIONING AND HEAT PUMP HOMEOWNER’S ROUTINE MAINTENANCE RECOMMENDATIONS We strongly recommend a bi-annual maintenance checkup be performed before the heating and cooling seasons begin by a qualified servicer. Replace or Clean Filter Clean Outside Coil (Qualified Servicer Only) IMPORTANT NOTE: Never operate unit without a filter installed as dust and lint will build up on internal parts resulting in loss of efficiency, equipment damage and possible fire.
  • Page 12: Customer Feedback

    We are very interested in all product comments. Please fill out the feedback form on one of the following links: Goodman® Brand Products: (http://www.goodmanmfg.com/about/contact-us). You can also scan the QR code on the right for the product brand you purchased to be directed to the feedback page.