Connecting Cables - Cisco ASR 901S Series Installation Manual

Hide thumbs Also See for ASR 901S Series:
Table of Contents

Advertisement

Installing the Router
When connecting the router AC power connector, always connect the router end of the cable first. When
Caution
removing the AC power connector, always disconnect the router end of the cable last.
Procedure
Step 1
Verify that the unit is grounded as described in
Step 2
Turn off power to the AC power source at the designated circuits.
Step 3
Align the notch in the AC power cable with the key in the router AC power connector, then push the cable
connector into the router connector. When the cable connector is fully seated, rotate the cable connector ring
clockwise until hand-tight.
Step 4
Confirm that the router antenna is connected to the router before you apply power to the router.
Step 5
Connect the other end of the AC power cable to the power source, using the instructions that came with the
connecting device.
Step 6
Turn on AC power at the designated circuits. The router will power on and boot the software image.

Connecting Cables

This section describes how to connect the Cisco ASR 901S Series Aggregation Services Router to external
devices and networks. Follow the procedures in this section based on your network configuration and
requirements.
To comply with the Telcordia GR-1089 NEBS standard for electromagnetic compatibility and safety,
Caution
connect the RJ45, Management Ethernet, Alarm, and Console ports only to intra-building or unexposed
wiring or cable. The intra-building cable must be shielded and the shield must be grounded at both ends.
The intra-building ports of the equipment or subassembly must not be metallically connected to interfaces
that connect to the OSP or its wiring. These interfaces are designed for use as intra-building interfaces
only (Type 2 or Type 4 ports as described in GR-1089-CORE) and require isolation from the exposed
OSP cabling. The addition of Primary Protectors is not sufficient protection in order to connect these
interfaces metallically to OSP wiring.
Caution
To comply with the Telcordia GR-1089 NEBS standard for electromagnetic compatibility and safety,
connect the RJ45 ports to intra-cell site wiring or cable. The intra-cell site cable must be shielded and the
shield must be grounded at both ends. The intra-cell site ports of the equipment or subassembly must not
be metallically connected to interfaces that connect to the OSP or its wiring. These interfaces are designed
for use as intra-cell site interfaces only (Type 3a or Type 5a ports as described in GR-1089-CORE) and
require isolation from the exposed OSP cabling. The addition of Primary Protectors is not sufficient
protection in order to connect these interfaces metallically to OSP wiring.
OL-29732-01
Grounding the Router, on page
Cisco ASR 901S Series Aggregation Services Router Hardware Installation Guide

Connecting Cables

45.
57