Application Information - McQuay MWM-LW Technical Manual

Chilled water fan coil units
Table of Contents

Advertisement

Application Information

Application Information
Model: MWM Series
Operating Limits:
Thermal carrier : Water
Water temperature : 4°C ~ 10°C (Cooling), 35°C ~ 50°C (Heating)
Maximum water pressure : 16 bar
Air temperature : (as below)
Cooling Mode
Temperature
Minimum indoor
temperature
Maximum indoor
temperature
Model: MCK Series
Operating Limits:
Thermal carrier : Water
Water temperature : 4°C ~ 10°C (Cooling), 35°C ~ 50°C (2 Pipes), 35°C ~ 70°C (4 Pipes)
Maximum water pressure : 16 bar
Air temperature : (as below)
Cooling Mode
Temperature
Minimum indoor
temperature
Maximum indoor
temperature
Model: MCC Series
Operating Limits:
Thermal carrier : Water
Water temperature : 5 ~ 50°C
Maximum water pressure : 16 bar
Air temperature : (as below)
Cooling Mode
Temperature
Minimum indoor
temperature
Maximum indoor
temperature
Model: MDB Series
Operating Limits:
Thermal carrier : Water
Water temperature : 4°C ~ 10°C (Cooling), 35°C ~ 70°C (Heating)
Maximum water pressure : 16 bar
Air temperature : (as below)
Cooling Mode
Temperature
Minimum indoor
temperature
Maximum indoor
temperature
9
Ts °C/°F
Th °C/°F
19.0 / 66.2
14.0 / 57.2
32.0 / 89.6
23.0 / 73.4
Ts °C/°F
Th °C/°F
16.0 / 60.8
11.0 / 51.8
32.0 / 89.6
23.0 / 73.4
Ts °C/°F
Th °C/°F
19.0 / 66.2
14.0 / 57.2
32.0 / 89.6
23.0 / 73.4
Ts °C/°F
Th °C/°F
19.0 / 66.2
14.0 / 57.2
32.0 / 89.6
23.0 / 73.4
Heating Mode
Temperature
Minimum indoor
temperature
Maximum indoor
temperature
Ts: Dry bulb temperature.
Heating Mode
Temperature
Minimum indoor
temperature
Maximum indoor
temperature
Ts: Dry bulb temperature.
Heating Mode
Temperature
Minimum indoor
temperature
Maximum indoor
temperature
Ts: Dry bulb temperature.
Heating Mode
Temperature
Minimum indoor
temperature
Maximum indoor
temperature
Ts: Dry bulb temperature.
Ts °C/°F
Th °C/°F
15.0 / 59.0
-
27.0 / 80.6
-
Th: Wet bulb temperature.
Ts °C/°F
Th °C/°F
16.0 / 60.8
-
30.0 / 86.0
-
Th: Wet bulb temperature.
Ts °C/°F
Th °C/°F
15.0 / 59.0
-
27.0 / 80.6
-
Th: Wet bulb temperature.
Ts °C/°F
Th °C/°F
15.0 / 59.0
-
27.0 / 80.6
-
Th: Wet bulb temperature.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mcm-dwMcm-ewMcc-cwMdb-bwMck-ewMck-cw

Table of Contents