Summary of Contents for McQuay MWM-G2W
Page 1
Technical Manual MFCU_(ii) Supercedes: MFCU_(i) Fan Coil Units Models: MWM-G2W MCM-DW MCM-CW/EW MCK-AW/CW MCC-CW MDB-BW En g i n e e re d f o r e x i b i l i t y a n d p e r f o r m a n c e . ™...
Indoor M WM 010 G2 W – A X AB Brand Product Specification Variation M : McQuay Model Name WM : Wall Mounted Split Type CK : Ceiling Cassette Split Type Type of ref. connection CM : Ceiling Exposed Split Type...
MFCU_(ii) Application Information Application Information Operating Range Operating Limits: Thermal carrier : Water Water temperature : 5 ~ 50°C Maximum water pressure : 16 bar Air temperature : (as below) Cooling Mode Heating Mode Temperature Ts °C/°F Th °C/°F Temperature Ts °C/°F Th °C/°F Minimum indoor...
Page 12
Application Information MFCU_(ii) Model : MWM 007/010/015G2W (IONIZER) Model : MWM 020/025G2W (IONIZER)
Page 13
MFCU_(ii) Application Information Model : MCM Series / MCC Series / MCK-AW/CW MCK-AWH 4 pipes system controller board setting A) Model selection The standard controller board (W2.0) comes with a default setting for model selection. Please select the model accordingly by using jumper.
Page 14
Application Information MFCU_(ii) System Model Function 2 Pipe M1 - Cooling or Heating System Model 1 M2 - Cooling or Heating with Auxiliary Heater Model 2 4 Pipe M3 - Cooling Only with Boiler System Model 3 M4 - Cooling or Heating with Boiler Model 4 B) Valve, Heat and Fan priority selection Jumper...
Page 15
MFCU_(ii) Application Information C) Others The controller board comes with other option. i) Unoccupied Mode If the dry contact is closed, the Unoccupied mode is activated and vice versa. When Timer On is active, system goes back to Occupied mode. The dry contact connection points can be connected parallel with other fan coil unit (FCU) boards.
Page 16
Application Information MFCU_(ii) Water Piping Connection The indoor unit is equipped with water outlet and inlet bare connection. There is an air-vent for air purging that is fitted at the outlet water header. 3 ways solenoid valve is required for cycling off or bypass the chilled water. Black steel pipe, polyethrene pipe, PVC pipe and copper tube recommended in field installation.
Page 17
MFCU_(ii) Application Information Piping Support All water mains must be adequately supported to carry the necessary weight involved, provisions must be made by the installing contractor to allow for adequate free movement of all vertical and horizontal risers and run outs. Due to the fact that cold water will be circulated through the water mains, a sizeable movement of the water mains can be expected due to contraction.
Page 18
Application Information MFCU_(ii) Cable Size Wall Mounted Model Unit MWM 007/010/015/020/025G2W MWM 301W Power supply cable size* mm² Number of wire Recommended fuse* MCK 020/025/030/ MCK 020/025/030/ Model Unit MCK 010/015/020CW 040/050AW 040/050AWH mm² Power supply cable size* Number of wire Recommended fuse* Model Unit...
MFCU_(ii) Sound Data Sound Data Sound Pressure Level Wall Mounted Split Type Overall 1/1 Octave Sound Pressure Level (dB, reference 20µPa) Noise Model Speed 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz (dBA) Criteria High Medium MWM007G2W High MWM010G2W Medium High MWM015G2W Medium High...
Page 20
Sound Data MFCU_(ii) Ceiling Exposed Split Type 1/1 Octave Sound Pressure Level (dB, ref 20μPa) Overall Noise Model Speed 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz (dBA) Criteria High Medium MCM020DW High Medium MCM025DW High Medium MCM030DW High MCM040DW Medium High MCM050DW Medium...
Page 21
MFCU_(ii) Sound Data Ceiling Concealed Fan Coil Unit 1/1 Octave Sound Pressure Level (dB, reference 20µPa) Overall Noise Speed Model Criteria 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz (dBA) 125 Hz High MCC010CW Medium High MCC015CW Medium High...
MFCU_(ii) Performance Data Performance Data Unit Selection Procedure The cooling and heating capacities of the fan coil units can be determined by the Cooling Capacity Perfor- mance Chart and Heating Capacity Performance Chart in the following pages based on nominal air flow at standard water temperature.
Page 60
Performance Data MFCU_(ii) Step 4 If air flow value is different from the nominal value(high speed), then refer to specification from Page 40 to 42 for the air flow required (medium or low speed). Determine the total and sensible correction factor from Air Flow Capacity Correction Factor (Page 40 to 42) Step 5 If the unit is to operate at an altitude above sea level, multiply the capacity correction factors by an Altitude...
Page 61
MFCU_(ii) Performance Data Step 2 Refer to Page 40 to 42, the air flow correction factor at high speed is 1.0 Step 3 As the unit is operating at 600m above sea level, the Altitude correction factor is 0.98 total and 0.93 sensible. Step 4 Multiply the cooling capacities obtained from step 1 (as per specification and design condition) by correction factors from (2) and (3)
Page 133
MFCU_(ii) Outlines & Dimensions Model: MDB 075BW Note: Dimension in mm Model: MDB 100BW Note: Dimension in mm...
Page 134
Outlines & Dimensions MFCU_(ii) Model: MDB 125BW (Horizontal Air Discharge, Right Piping) Note: Dimension in mm Model: MDB 150BW (Horizontal Air Discharge, Right Piping) Note: Dimension in mm...
Page 135
MFCU_(ii) Outlines & Dimensions Model: MDB 125BW (Vertical Air Discharge, Left Piping) Note: Dimension in mm Model: MDB 150BW (Vertical Air Discharge, Left Piping) Note: Dimension in mm...
Page 138
Wiring Diagrams MFCU_(ii) Model: MCK 020/025/030/040/050AW E 1PHASE N 220/240VAC 50HZ To 3 WAY VALVE Model: MCK 010/015/020CW E 1PHASE N 220/240VAC 50HZ To 3 WAY VALVE...
Page 139
MFCU_(ii) Wiring Diagrams Model: MCK 020/025/030/040/050AWH E 1PHASE N 220/240VAC 50HZ To 3 WAY To 3 WAY VALVE VALVE...
Page 140
Wiring Diagrams MFCU_(ii) Model: MCM 020/025/030/040/050DW E 1PHASE N 220/240VAC 50HZ To 3 WAY VALVE Model: MCM 007/015CBW...
Servicing & Maintenance MFCU_(ii) Servicing & Maintenance Caution Moving machinery and electrical power hazards. May cause severe personal injury or death. Disconnect from main power supply before servicing equipment. The unit is designed to give long life operation with minimum maintenance required. However, it should be regularly checked and the following items should be given due attention.