Advertisement

INSTALLATION, OPERATING AND
MAINTENANCE INSTRUCTIONS
N2 Condens
N 2 Condens : 664Y5000 • C
21.8 kW
en
1
EN
FR
NL
ES
IT
DE
PL
RU

Advertisement

Table of Contents
loading

Summary of Contents for ACV N2 CONDENS

  • Page 1 INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS N2 Condens 21.8 kW N 2 Condens : 664Y5000 • C...
  • Page 2: Table Of Contents

    TABLE OF CONTENTS GENERAL RECOMMENDATIONS .................. 4 USER GUIDE ..........................5 APPLIANCE DESCRIPTION ....................6 TECHNICAL CHARACTERISTICS ................... 8 Electrical characteristics ......................8 Dimensional characteristics ......................9 Combustion characteristics ......................11 Hydraulic characteristics ......................12 Characteristics of flue connection ..................13 Operating limits .......................... 14 INSTALLATION ........................15 Contents included in delivery ....................
  • Page 3 TABLE OF CONTENTS COMMISSIONING ........................29 Commissioning safety instructions ..................29 Tools required for commissioning ..................29 Checks before bringing into service ..................29 Preliminary filling of the heating system ................30 Starting the boiler ........................30 Full flush of the heating system .....................30 MAINTENANCE ........................31 Safety instructions for maintenance ..................
  • Page 4: General Recommendations

    GENERAL RECOMMENDATIONS These instructions contain important information necessary for the installation, commissioning and maintenance of the boiler. These instructions must be given to the user who should keep them in a safe place after carefully reading them. We accept no liability in the event of damage caused by failure to comply with the instructions appearing in this technical manual.
  • Page 5: Fr User Guide

    USER'S GUIDE 1. Boiler on/off switch 2. Summer/winter switch (is used to turn the heating circulator on and off). 3. Safety warning indicator (lights up when the temperature of the flue gas or water of the primary system is too high). 4.
  • Page 6: Appliance Description

    APPLIANCE DESCRIPTION The N2 Condens condensing fuel oil boiler is a heat generator that enables the water for the central heating and DHW heater to be reheated (if the latter is connected to the boiler). 1. Condenser 2. Flue outlet 3.
  • Page 7 APPLIANCE DESCRIPTION 9. Minimum thermostat 10. Heating flow 11. Heating return 12. Removable panels 13. Condensate trap 14. Condensate exhaust hose 15. Electrical connection socket of the boiler 16. Connection socket of flue gas safety thermostat (optional) 17. Drain valve N 2 Condens : 664Y5000 •...
  • Page 8: Technical Characteristics

    TECHNICAL CHARAC TERISTICS ELECTRICAL CHARACTERISTICS Main electrical characteristics N2 Condens Nominal voltage Nominal frequency Nominal intensity Wiring diagram 1. On/Off switch Y/Gr 2. Minimum thermostat 45 °C 3. Summer/winter switch 4. Safety thermostat 5. Burner 6. Safety warning indicator 7. Room thermostat (optional) 8.
  • Page 9: Dimensional Characteristics

    TECHNICAL CHARAC TERISTICS DIMENSIONAL CHARACTERISTICS Boiler dimensions N2 Condens A = Width B = Height C = Depth Volume of the combustion chamber 42.3 Height Combustion chamber Width Depth Empty weight 235 mm 80 mm 50 mm 105 mm N 2 Condens : 664Y5000 • C...
  • Page 10 TECHNICAL CHARAC TERISTICS N2 Condens Overall dimensions of boiler Recommended Minimum A (mm) B (mm) 1000 C (mm) D (mm) The two lateral rear panels allow access to the components inside the boiler from the left or right hand side.
  • Page 11: Combustion Characteristics

    TECHNICAL CHARAC TERISTICS COMBUSTION CHARACTERISTICS Main characteristics N2 Condens Fuel type EL fuel oil Heat flow (input - NCV) 22.4 Output rate (80/60°C) 21.8 Output rate (50/30°C) 23.3 Efficiency at 30% load (EN 677) Efficiency at 100% load (80/60°C) 97.5 Efficiency at 100% load (50/30°C) 103.5...
  • Page 12: Hydraulic Characteristics

    TECHNICAL CHARAC TERISTICS HYDRAULIC CHARACTERISTICS Main hydraulic characteristics N2 Condens Boiler water capacity Heating flow connection (female) Ø 1" Heating return connection (female) Ø 1" Max operating pressure of the heating circuit Heating exchanger pressure drop (∆t = 20°C) mbar...
  • Page 13: It Characteristics Of Flue Connection

    TECHNICAL CHARAC TERISTICS CHARACTERISTICS OF FLUE CONNECTION Flue characteristics N2 Condens Connection type Ø of boiler connection to flue Ø of minimum flue pipe L = Maximum length of Ø 80 mm flue pipe Maximum flue gas T° °C Flue gas temperature - Max. ouput power 80/60°C °C...
  • Page 14: Operating Limits

    TECHNICAL CHARAC TERISTICS OPERATING LIMITS Maximum service pressure - Primary circuit : ......................3 bar Operating temperature - Maximum temperature of the primary circuit : ..........90°C Water quality See Recommendations for the prevention of corrosion and scaling Fuel oil quality •...
  • Page 15: De Installation

    The appliances are delivered tested and separately packaged. Contents of package No. 1 Contents of package No. 2 • N2 Condens boiler. • A blue flame fuel oil burner BMR 33. • Multilingual installation, operating and • Multilingual installation, operating and maintenance instructions.
  • Page 16: How To Move The Boiler

    INSTALLATION HOW TO MOVE THE BOILER Move using a hand truck Use a hand truck suitable for the weight of the boiler. Minimum door and hall width required to pass the boiler through A = maximum boiler width B = maximum boiler length C = door width D = hall width Width of corridor:...
  • Page 17: Tools Required For Installation

    INSTALLATION TOOLS REQUIRED FOR INSTALLATION INSTALLATION INSTRUCTIONS General comments The connections (electrical, flue and hydraulic) must be made in accordance with current standards and regulations. Important recommendations for the correct operation of the appliance The boiler must be installed in a dry and weather-protected room. Make sure to position the appliance so that it is always easily accessible.
  • Page 18 INSTALLATION Make a slight gradient of 3% to the horizontal flue gas pipes so that the acid condensation water runs towards a condensate collector and does not damage the heating unit. Do not store any flammable or corrosive materials, or paint, solvents, salts, chlorine products or any other detergent products in the vicinity of this appliance.
  • Page 19: Recommendations For Preventing Corrosion And Scaling

    A deaerator (on the boiler flow line) combined with a dirt separator (upstream of the boiler) must be installed according to the manufacturer's instructions. - ACV recommends using additives that keep the oxygen in solution in the water, such as Fernox (www.fernox.com) and Sentinel (www.sentinel-solutions.net) products.
  • Page 20 INSTALLATION 4. Limit the carbonate concentration in the water - The fill water must be softened if its hardness is higher than 20° fH (11,2° dH). - Check regularly the water hardness and enter the values in the service log. - Water hardness table : Water hardness °fH...
  • Page 21: Boiler Preparation

    INSTALLATION BOILER PREPARATION N 2 Condens : 664Y5000 • C...
  • Page 22 INSTALLATION N 2 Condens : 664Y5000 • C...
  • Page 23: Ru Fitting The Burner

    INSTALLATION FITTING THE BURNER N 2 Condens : 664Y5000 • C...
  • Page 24: Electrical Connection

    INSTALLATION ELECTRICAL CONNECTION 1. Installation heating pump 2. Room thermostat 3. Flue gas safety thermostat for synthetic flue pipe 4. Link (to be removed before connecting the room thermostat ➋) 5. Link (to be removed before connecting the flue gas safety thermostat ➌) 230 V ~ 50HZ N 2 Condens : 664Y5000 •...
  • Page 25: Flue Connection

    INSTALLATION FLUE CONNECTION Operation dependent on ambient air (B23 installation) To ventilate the installation room, it is necessary to provide – in accordance with the regulation on combustion – a vent to the open air from the room with a minimum cross-section of 150 cm or to make a connection with other rooms in order to release the combustion air.
  • Page 26: Hydraulic Connections

    INSTALLATION HYDRAULIC CONNECTIONS 1. Heating isolating valve Do not fit a thermostatic valve on 2. Check valve radiators located in rooms equipped 3. Installation heating pump with room thermostats. 4. Mixing valve 5. Safety group 6. Primary circuit filling valve 7.
  • Page 27: Connection To A Hot Water Tank

    11. Room thermostat 12. Contact sensor When you use an ACV control or a control of a different make,  please assure that you have adjusted the starting temperature of the heating pump (3) above 43°C. N 2 Condens : 664Y5000 • C...
  • Page 28: Fuel Oil Connection

    11. Room thermostat 6. Primary circuit filling valve When you use an ACV control or a control of a different make,  please assure that you have adjusted the starting temperature of the heating pump (3) above 43°C. FUEL OIL CONNECTION...
  • Page 29: Commissioning

    COMMISSIONING COMMISSIONING SAFETY INSTRUCTIONS General comments In normal operation, the burner starts automatically when the boiler temperature is lower than that of the set point. Important safety recommendations Only an approved installer is authorized to access the components inside the control panel.
  • Page 30: Preliminary Filling Of The Heating System

    COMMISSIONING PRELIMINARY FILLING OF THE HEATING SYSTEM • Fill the primary system with water from the mains supply until a pressure of approx. 1.5 bar is obtained in the system. • Bleed the whole system. STARTING THE BOILER Starting the burner •...
  • Page 31: Maintenance

    MAINTENANCE SAFETY INSTRUCTIONS FOR MAINTENANCE Important recommendations for electrical safety Before starting any work, stop the boiler and disconnect the appliance’s electrical supply. Important safety recommendations The water flowing from the drain valve is very hot and can cause very serious burns.
  • Page 32: Cleaning The Combustion Assembly

    MAINTENANCE ANNUAL MAINTENANCE Cleaning the combustion assembly It is recommended to clean the boiler on a warm day as it will be switched off for a few hours. Cleaning the burner 1. Open the front panel. 2. Loosen the burner flange and put the burner in the maintenance position (see burner instructions).
  • Page 33: Inspection Of Safety Devices

    MAINTENANCE Cleaning the trap 1. Loosen the trap ring. 2. Check that the condensate exhaust pipe is not blocked. 3. Clean the trap with soap and water. 4. Make sure to leave enough water in the trap before reassembly, or pour 20 cl of water in the condenser before reassembly.
  • Page 34: Declaration Of Conformity - Ce

    DECLARATION OF CONFORMITY - CE ACV International Name and address of manufacturer: SA / NV Kerkplein, 39 B-1601 Ruisbroek Oil condensing boiler Description of product type: Models: N 2 Condens 0461BU0936 CE # : We declare hereby that the appliance specified above is conform to the type model described in the CE certificate of conformity to the following directives:...
  • Page 35 N 2 Condens : 664Y5000 • C...
  • Page 36 N 2 Condens : 664Y5000 • C...

Table of Contents