Water quality requirements

Note
Observing the following requirements is
necessary to safeguard your warranty
rights.
Prevention of damage due to scaling
Prevent excessive scale build-up (calcium carbonate) on the heating surfaces. For
heating systems with operating temperatures up to 100 °C, the VDI Directive 2035
sheet 1 "Prevention of heating system damage – scaling in DHW and hot water heat-
ing systems" applies [in Germany] together with the following standard values (see
also the relevant explanations in the original directive).
Total heating output
kW
> 50 to ≤ 200
> 200 to ≤ 600
> 600
The standard values assume the follow-
ing:
■ The total volume of fill and top-up
water during the system's service life
will not exceed three times the water
content of the heating system.
■ The specific system volume is less
than 20 l/kW heating output. In multi
boiler systems, apply the output of the
smallest boiler.
■ All measures to prevent corrosion on
the water side in accordance with VDI
2035 sheet 2 have been implemented.
62
The manufacturer's warranty excludes
damage due to corrosion and scaling.
Total of alkaline earths
3
mol/m
≤ 2.0
≤ 1.5
< 0.02
Soften the fill and top-up water in heating
systems operating under the following
conditions:
■ The total of alkaline earths in the fill &
top-up water exceeds the standard
value.
■ Higher fill and top-up water volumes
are expected.
■ The specific system volume is higher
than 20 l/kW heating output. In multi
boiler systems, apply the output of the
smallest boiler.
Total hardness
°dH
≤ 11.2
≤ 8.4
< 0.11