Commissioning, inspection, maintenance
Further details regarding the individual steps
Total hardness
Feedwater
Boiler water Boiler
The pH value should be between 8.2 and 9.5.
Checking the diaphragm expansion vessel and system pressure
Note
Observe the details provided by the
manufacturer of the diaphragm expan-
sion vessel.
Carry out this test on a cold system.
1. Drain the system until the pressure
gauge indicates "0" or close the cap
valve on the diaphragm expansion
vessel and reduce the pressure in
this vessel.
30
pH value
Water treatment
Medium
water
2. If the pre-charge pressure of the dia-
3. Top up with water until the charge
(cont.)
Metering
volume
phragm expansion vessel is lower
than the static system pressure, top
up with nitrogen until the pre-charge
pressure is 0.1 to 0.2 bar higher.
pressure of the cooled system is 0.1
to 0.2 bar higher than the pre-charge
pressure of the diaphragm expansion
vessel.
Permiss. operating pressure: 4 bar