Viessmann VITOCROSSAL 200 Service Instructions Manual page 37

Type cm2 gas condensing boiler with matrix radiant burner
Hide thumbs Also See for VITOCROSSAL 200:
Table of Contents

Advertisement

Burner control unit
Setting
Rated burner heating output
Parameter set 4
≙ 246 kW
ON
ON
1 2 3 4 5 6 7 8
Parameter set 5
≙ 311 kW
ON
ON
1 2 3 4 5 6 7 8
Acknowledging a parameter set
A flashing "P" is shown under "Status" if a parameter set is changed via the DIP switch
or if the burner control unit has been replaced. The numbers shown under Service
indicate the selected parameter set (see page 36).
Status Service
"U" will appear under "Service" if an invalid DIP switch setting is selected.
Status Service
1. Check the DIP switch setting; if
required, change it in accordance
with page 36 .
(cont.)
Setting
Reduced burner heating output
Parameter set 10
≙ 173 kW
ON
1 2 3 4 5 6 7 8
Parameter set 11
≙ 218 kW
ON
ON
1 2 3 4 5 6 7 8
2. Press b and a simultaneously for
approx. 2 s.
The selected parameter setting has
been accepted when "P" no longer
flashes and the memory LED illumi-
nates.
37