Honeywell ECC-50/100 Instruction Manual page 54

Emergency command center, multipurpose emergency voice evacuation panels
Table of Contents

Advertisement

Installation
Primary/Secondary with Expander
and Optional Amplifier
• 50W for primary, 50W for secondary
• Eight Class B or Class A Outputs
• Optional amplifier supplies all
secondary circuits
• ECC-CE6 adds 3 primary and 3
secondary circuits
• No backup
Figure 2.40 Primary/Secondary with Expander and Optional Amplifier
Applications With Backup
Primary with Backup
• One amp at 50W
• One Class B or Class A Output
• Optional amplifier is the backup
Primary with Expander and Backup
• 50W for primary, 50W for backup
• Four Class B or Class A Outputs
• ECC-CE6 adds 3 primary speaker
circuits
• Optional Amplifier is the backup
54
Figure 2.41 Primary with Optional Amplifier Backup
Figure 2.42 Primary with Expander and Optional Amplifier Backup
Emergency Command Center Manual — P/N LS10001-000FL-E:G 5/3/2016
zone button
Speaker Circuit Connections
TB20 on main control board
1
Primary
50W
circuit
2
TB21 on main control board
3
TB1 on ECC-CE6, primary power
Secondary
50W
amp
4
TB4 on ECC-CE6, secondary power
TB2 on ECC-CE6, primary power
5
CE6
TB5 on ECC-CE6, secondary power
6
TB3 on ECC-CE6, primary power
7
TB6 on ECC-CE6, secondary power
8
zone button
1
Primary
50W
circuit
Backup
50W
amp
zone button
1
Primary
50W
circuit
2
Primary/
3
Backup
CE6
4
Backup
50W
amp
Installation of Option Modules
Speaker Circuit Connections
TB20 on main control board
Speaker Circuit Connections
TB20 on main control board
TB1 on ECC-CE6
TB2 on ECC-CE6
TB3 on ECC-CE6