(1) Remove the terminal block cover on the lower right side of the unit's
rear panel.
(2) Connect the units that need to be backed up. Two types of connections
can be made.
1) To turn ON/OFF at the same timing as that of output receptacle B:
L1B terminal: Connect the line
L2B terminal: Connect the neutral line
2) To turn ON/OFF at the same timing as that of output receptacle C:
L1C terminal: Connect the line
L2C terminal: Connect the neutral line
Run the wires to be connected through the hole in the included terminal block cover (with cable
clamp and cable guard tube). (See Figure 1.)
If you have trouble running the wire through the hole, loosen the cable clamp dial by turning it
counter-clockwise.
Connect the ground wire to the G terminal.
Use a fl at head screwdriver to loosen the terminal block screws, insert the wire, and then retighten
the screws. (See Figure 2.) Refer to Table 1 for wire sizes.
Figure 1
(3) Insert the tab on the right side of the terminal block cover (with
cable clamp) into the unit's body, and fasten the previously
removed screws to the two locations on the left side of the cover.
Tighten the cable clamp dial to stabilize the wire. (See Figure 2.)
(2) When using the included UPS monitoring software and the Windows standard UPS service, use a
connection cable to connect the unit to the PC.
See also "7. Using the UPS monitoring software and Contact Signal" on page 66.
* If you do not use the UPS monitoring software and Contact Signal, this step is not required.
(3) When the installation and connection is complete, connect the AC Input Plug of the UPS to a wall outlet
(commercial power).
Make sure to connect the AC input plug of the unit into a wall outlet
(commercial power) with rated input voltage (200 to 240V AC).
● Connecting to a wall outlet (commercial power) of a different rated input voltage may
result in fi re.
● The unit may fail.
Figure 2
Table 1
Connectable wire size
Amount of stripped wire
Tightening torque
Recommended cable size
1.0 to 2.5 mm
5.5mm
0.9Nm (8 lb-in)
2
2mm
(AWG14)
Caution
1002
3002
BU
SW / BU
<BU1002SW>
G
L2C
L2B
L1C
L1B
C
Figure 3
2
SW
1
B
2
3
4
5
6
7
8
9
10
23